Small-Signal Stability of HVDC-Connected Offshore Wind Farms Under Weak-Grid Conditions
Authors: , ,
Search Articles
Abstract: This paper investigates the small-signal stability of an offshore wind farm connected to a weak
onshore AC network through voltage-source-converter-based high-voltage direct-current transmission. An
eight-state reduced-order model represents the offshore grid-forming converter, onshore phase-locked loop (PLL),
active-power control, DC-link voltage regulation, and battery energy storage system (BESS). Eigenvalue analysis
is used to assess the effects of short-circuit ratio (SCR), PLL natural-frequency scaling, wind-power loading, and
BESS inclusion. Reducing the SCR from 10 to 1 decreases the damping ratio of the PLL-related mode from 0.571
to 0.285. Increasing the PLL scaling factor from 0.5 to 2.0 raises the modal frequency from 7.41 Hz to 29.51 Hz
while maintaining an approximately constant damping ratio. Wind-loading effects are comparatively small, and
BESS inclusion provides supplementary reactive-power and voltage support without materially changing the
principal PLL-related mode.
Keywords:
Battery energy storage system, eigenvalue analysis, grid-following converter, HVDC transmission, offshore wind integration, phase-locked loop, small-signal stability, weak grid
Pages: 408-428
DOI: 10.37394/232016.2026.21.32