Modeling, Integration and Simulation of the Photovoltaic Power Plant
Considering LVRT Capability and Transient Voltage Stability
ABDELAZIZ SALAH SAIDI1,2(Member, IEEE), OSAMA ALI ZEMI3, LINA ALHMOUD4,
and MUHAMMAD UMAR MALIK5
1Electrical Engineering Department, King Khalid University, Abha 61421, KINGDOM OF SAUDI ARABIA
2Laboratoire des Systèmes Electriques, Ecole Nationale d’Ingénieurs de Tunis,
Université de Tunis El Manar, TUNISIA
3National Grid company, Project Management Office, Central Operation Area, KINGDOM OF SAUDI ARABIA
4Electrical Power Engineering Department, Hijjawi Faculty for Engineering Technology, Yarmouk University, Irbid 21163, JORDAN
5Grid Studies Department, National Grid Company, KINGDOM OF SAUDI ARABIA
Abstract: - This paper investigates how high photovoltaic energy penetration impacts dynamic performance and
voltage regulation of the modified IEEE-9 bus grid. The transmission power system was modeled and simulated
using PSCAD-EMTDC software to conduct the study. Load flow analysis is implemented to explore the power
system’s capability to incorporate the desired photovoltaic power. Moreover, the study is based on time response
simulations to grid disturbances. The supply and control of reactive power from solar power generation plants are
becoming critical issues to study because they can facilitate the integration of PV in power grids under different
operating conditions. Network-related faults like a PV solar power plant event outage, a three-phase short-circuit
at a conventional bus, and a voltage dip at the PV solar power plant have been considered. The results will
help identify the protective devices and strategies needed to maintain the stability and reliability of the system
operation and transient analysis of the network under external power network fault and recovery operation. Thus,
it has practical significance for real utility studies. Moreover, this comprehensive study will be a valuable guide
for assessing and improving the grid’s performance under the study of any other grids, which also gives the vast
potential and need for solar energy penetration into the grid systems.
Key-Words: - Photovoltaic power plant, PSCAD, Static load, Modeling, Transient voltage stability, LVRT
capability.
Received: November 23, 2022. Revised: November 24, 2023. Accepted: December 27, 2023. Published: December 31, 2023.
1 Introduction
Voltage stability is the ability of the system to pre-
serve acceptable voltages at all buses in the system
under normal conditions, especially after being ex-
posed to a disturbance. Apower system is said to have
gotten into a state of voltage instability when a distur-
bance results in a progressive and uncontrollable very
low voltage. The power system may undergo voltage
collapse if the post-disturbance equilibrium voltages
near loads are below acceptable limits. Voltage col-
lapse is a process that leads to a decline in voltage pro-
file, causing voltage instability in a significant part of
the system. Voltage stability is sometimes called load
stability [1]. The present transmission systems are in-
creasingly stressed due to economic and environmen-
tal constraints. Voltage stability problems usually oc-
cur in heavily stressed systems. Thus, voltage secu-
rity means the ability of a system not only to operate
stable but also to remain stable following a contin-
gency or load increase. Voltage stability can be classi-
fied based on time frame: short-term voltage stability
and long-term voltage stability; and the type of dis-
turbance: small disturbance voltage stability and sig-
nificant disturbance voltage stability [2]. Short-term
voltage stability typically lasts for a few seconds. The
analysis requires a solution of appropriate differential
equations. It involves dynamics of fast-acting com-
ponents such as automatic voltage regulator (AVR),
turbine, and governor dynamics. Long-term voltage
stability is mainly due to the considerable distance
between the generator and the load. It involves the
dynamics of slow-acting equipment such as a tap-
changing transformer. The time frame is within a few
minutes to tens of minutes. This type of voltage insta-
bility may be prevented by load shedding and reactive
power compensation [3].
Large disturbance voltage stability measures the
system’s ability to control voltage at all buses follow-
ing significant disturbances such as generation loss,
load loss, and systems faults. This stability can be de-
termined by assessing the system’s dynamic perfor-
mance over sufficient time to capture device interac-
tions such as generator field current limiter and un-
load tap changing transformers. Meanwhile, in small-
distance voltage stability, following any minor distur-
bances at any given operating state, the voltage close
to the load remains fixed or near the pre-disturbance
values [4]. The load flow study is the first step in
analyzing the power system from the capacity stand-
point to investigate generation sources, transformers,
and cables that match the intended loads. In addi-
WSEAS TRANSACTIONS on POWER SYSTEMS
DOI: 10.37394/232016.2023.18.35
Abdelaziz Salah Saidi, Osama Ali Zemi,
Lina Alhmoud, Muhammad Umar Malik
E-ISSN: 2224-350X
340
Volume 18, 2023
tion, a load flow study points out locations in the
system where low-voltage or high-voltage conditions
may exist. The first step in a load flow study is to
create an accurate system model in a line diagram.
Computer programs like PSCAD can run simulations
on that power system to evaluate what-if scenarios for
load changes in contingent situations [5]. The itera-
tive process of a load flow simulation starts by us-
ing the load as a known quantity. Still, since current
flow is likely based on voltage and the voltage at a
particular node varies based on current flow, the pro-
gram needs to make an educated guess as to the total
power flowing from the source. Then, calculations
are performed until the mismatch of the estimation is
very close to the actual load specified. The load flow
simulation solves losses and voltage profiles [5], and
bold changes along the way are plotted on a single-
line diagram. Scenarios are created to determine if
new equipment is needed or if transformer tabs need
to be adjusted to compensate for the additional load.
The benefit of this study is that if the network size
is increased or new renewable generation sources are
added, starting from the base case model of the sys-
tem, Many alternative scenarios can be run until the
results are comfortable. At the end of this process, the
operator knows precisely the required changes needed
to optimize power flow and cost. Ways can be shown
to reduce energy bills or how to add more load to
the existing system for capacity reasons, voltage drop
consideration, or loss calculations to enhance tran-
sient voltage stability profile while improving voltage
levels throughout the system [6].
Power system stability and control are not con-
sidered new concerns. However, grid operators are
now paying extra attention to keeping the transmis-
sion systems stable to prevent the recurrence of large
blackouts that have affected many countries. Thus,
the power system network is under typical operating
conditions, and after being perturbed, it should be sus-
tained, stable, reliable, and secure, and the bus volt-
ages should be within limits. There are several ways
to approach voltage stability study [6]. However, it
can be helpful for operators to estimate the power
system’s closeness to voltage collapse before imple-
menting corrective measures and taking premedical
actions. Voltage stability analysis is still frequently
used in industries to calculate the P-V and Q-V curves
at specific load buses [7]. Numerous load flows often
produce these curves utilizing traditional techniques
and models. However, these techniques take a lot of
time and don’t offer enough valuable information to
address the stability issues. In [8], several reasons
electricity systems go through interruptions are listed.
Meanwhile, power system outages can be prevented
in several cases with sufficient system protection and
adequate awareness. Suppose the power system is
not equipped with suitable protection for the system
[9]. In that case, the power system is prone to unex-
pected factors such as external disturbances, compo-
nent failures, and parameter changes [9]. Hence, volt-
age instability is one of the problems causing power
interruptions and voltage collapse. The power sys-
tem utilized in this paper is the IEEE 9-bus test case.
The IEEE 9-bus test case represents a portion of the
Western System Coordinating Council (WSCC) [2],
[10]. Many researchers have studied it and a PV solar
power plant connected to bus 6. Integration of PV so-
lar power plants poses significant challenges. Thus, it
limits reactive power capability and causes a signifi-
cant voltage drop or rise in the system [11], [12].
The work assesses transient voltage stability in a
modified IEEE 9-bus in the presence of a photovoltaic
(PV) solar power plant and a three-phase short cir-
cuit at the most loaded bus in the system. The system
was modeled in PSCAD; a simulation study was per-
formed to investigate potential transient voltage sta-
bility based on the voltage profiles, active and reac-
tive power profiles, and system stability. The system
under different operating conditions is simulated and
analyzed. It aims to classify stability issues likely to
occur in the grid by identifying different scenarios to
enhance the industry’s understanding of the interac-
tion of PV solar power plants with other assets in the
system. In this work, the IEEE 9-bus is used to cre-
ate an equivalent standard test in PSCAD. The power
flow data system is available in [2]. After success-
fully validating the power flow, many scenarios are
simulated. (i) the pre-disturbance steady state is ob-
tained, (ii) a PV solar power plant is integrated into the
system at bus 8, and the dynamic performance is reg-
istered, (iii) the impact of a three-phase short circuit
takes place at the most loaded bus 8 while a sudden
disconnection of the PV solar power plant is simulated
and discussed. (iv) The impact of a three-phase short
circuit occurs at the most loaded bus 8 while recon-
nection of the PV solar power plant is analyzed.
The paper is organized such that Section 2 presents
the implementation of a PV solar power plant in
PSCAD. Section 3 describes the proposed system un-
derstudy of IEEE 9-bus before and after modifica-
tions. Section 4 presents the results of four scenarios:
base case, modified case with PV solar power plant,
modified case with PV solar power plant connected at
bus 6, and three-phase short circuit at bus 8 which is
the most loaded bus. Finally, the case after the sudden
disconnecting of the PV solar power plant in the pres-
ence of a fault of a three-phase short circuit. Section
5 presents the conclusion and future work.
2 PV plant model and control
PSCAD (Power Systems Computer Aided Design)
is a commercial international software for analyzing
WSEAS TRANSACTIONS on POWER SYSTEMS
DOI: 10.37394/232016.2023.18.35
Abdelaziz Salah Saidi, Osama Ali Zemi,
Lina Alhmoud, Muhammad Umar Malik
E-ISSN: 2224-350X
341
Volume 18, 2023
Figure 1: Grid-connected PV plant model using PSCAD software [13].
and simulating power and electrical systems. It was
officially developed by the engineering department
within Manitoba Hydro International Ltd. (MHI)
in 1983 in Canada. It is a comprehensive build-
ing, modeling, and simulating electromagnetic tran-
sient (EMT) studies. It includes an extensive li-
brary of power and energy models, including pas-
sive elements, control functions, and electrical ma-
chines. The integrated calculations and analysis soft-
ware, power flow calculation, short circuit calcula-
tion, motor starting, and transient stability. Models
include power system studies, HVDC and FACTS, re-
newable energy integration, electromagnetic transient
studies, and power equipment services. Thus, it intro-
duces a comprehensive and robust solution from sim-
ulation to real-time operational control for power gen-
eration, transmission systems, distribution, and uti-
lization. The functional expressions in each mod-
ule are very intuitive and easy to understand. Each
part’s simulation modules’ simulation results can also
be given as a report [13], [14].
Integrating PV solar power plants in PSCAD is
available under different operating conditions. There
are two switches, one to control the irradiation and the
other to control the temperature. The PV solar power
plant model mainly consists of arrays and converters
as shown in Figure 1. The PV Array is a PSCAD mod-
ule used to model the behavior of a solar photovoltaic
(PV) array. It typically contains a group of solar PV
panels connected in series and parallel to generate the
system’s required DC voltage and current. The main
function of the PV Array during the simulation of a
PV solar power plant is to model the behavior of the
solar PV array and its interaction with the other com-
ponents in the system, such as the boost converter,
voltage source converter, and LCL filter. Precisely,
the PV Array Box in PSCAD can model the behavior
of the solar PV array by generating DC power based
on the input irradiance and temperature values. The
DC power output is then sent to the boost converter
for voltage regulation. In addition, it can monitor the
DC voltage and current of the solar PV array to ensure
that they remain within the system’s operating range.
The PV Array Box can model the behavior of the indi-
vidual PV panels in the array by considering their tem-
perature coefficient, shading effects, and other factors
that affect their performance. The PV Array Box can
implement MPPT algorithms to optimize the power
output of the solar PV array by adjusting the input
voltage and current to ensure that the PV panels oper-
ate at their maximum power point [15], [16].
The specific settings and parameters of the voltage
source converter (VSC) in PSCAD may vary depend-
ing on the characteristics of the solar PV system and
the power grid. Therefore, it is essential to carefully
analyze the behavior of the solar PV system and adjust
the VSC settings accordingly to ensure proper perfor-
mance during the simulation. The boost converter is
a DC-DC converter commonly used in solar PV sys-
tems to step up the DC voltage produced by the PV
panels to a suitable level for the voltage source con-
verter (VSC) [17]. The main function of the boost
WSEAS TRANSACTIONS on POWER SYSTEMS
DOI: 10.37394/232016.2023.18.35
Abdelaziz Salah Saidi, Osama Ali Zemi,
Lina Alhmoud, Muhammad Umar Malik
E-ISSN: 2224-350X
342
Volume 18, 2023
converter during the simulation of a PV solar power
plant is to regulate the DC voltage to ensure that it
remains within the range required by the VSC. The
boost converter does this by adjusting the switch’s
duty cycle to control the current flow through an in-
ductor and a capacitor. The boost converter can also
provide other essential functions, such as maximum
power point tracking (MPPT), to optimize the power
output of the PV solar power plant by adjusting the
input voltage and current to ensure that the PV panels
operate at their maximum power point. Besides, the
boost converter can limit the input current to the VSC
or inverter to ensure that it remains within the rated
capacity of the device and does not cause overloading
or damage [18]. Also, the boost converter can detect
and protect against faults, such as overvoltage, under-
voltage, overcurrent, and short-circuit conditions, to
ensure that the PV solar power plant operates safely
and reliably. Besides, the VSC can adjust the phase
angle between the current and voltage waveforms to
improve the system’s power factor, reducing losses
and improving the system’s efficiency. Also, the VSC
can detect when the power grid is disconnected or ex-
periences a fault and automatically switch to islanding
mode to ensure that the PV solar power plant contin-
ues supplying power to critical loads. The VSC can
suppress the high-frequency harmonics generated to
ensure that the AC power injected into the grid meets
the relevant power quality standards [19].
3 System Under Study
The IEEE 9-bus system is a standard test case used
in power system analysis and research [1]. It consists
of nine buses, three generators, three loads, and trans-
mission lines and transformers, as shown in Figure 2.
Table 1,Table 2, and Table 3 summarize the per uni-
tized terminal conditions of each source, the transmis-
sion lines parameters, and PQ load model with 100
MVA, respectively. The base voltage levels are 16.5
kV, 13.8 kV, 18 kV, and 230 kV. The complex power
for each line is around hundreds of MVA each. The
generators are connected to Bus 1, Bus 2, and Bus 3.
Meanwhile, the loads at Bus 5, Bus 6, and Bus 8. This
system has a few voltage control devices. Thus, it is
easy to control. The purpose of the IEEE 9-bus sys-
tem is to provide a standard reference for researchers
to test and compare new power system analysis tech-
niques, such as load flow, transient stability, and fault
analysis. The system is also used for teaching pur-
poses in power system courses. Researchers use IEEE
9 bus systems to implement new ideas and concepts.
Indeed, the test was developed by the Western Sys-
tem Coordinating Council (WSCC). In transient sta-
bility studies, it is vital to have the pre-fault voltage
magnitude and phase angle at each bus and active and
reactive power on generation and transmission buses.
Table 1: Conditions of the IEEE 9-bus system.
Bus V (kV) δoActive power (pu) Reactive power (pu)
1 17.160 0.0 0.7163 0.2791
2 18.45 9.3507 1.63 0.049
3 14.145 5.142 0.85 -0.1145
Table 2: Transmission line characteristics of IEEE 9-
bus system.
From line To line R (pu/m) X (pu/m) B (pu/m)
4 5 0.0100 0.0680 0.1760
4 6 0.0170 0.0920 0.1580
5 7 0.0320 0.1610 0.3060
6 9 0.0390 0.1738 0.3580
7 8 0.0085 0.0576 0.1490
8 9 0.0119 0.1008 0.2090
Table 3: Load characteristics of IEEE 9-bus system.
Bus Active power (pu) Reactive power (pu)
5 1.25 0.50
6 0.90 0.30
8 1.00 0.35
A 25 MW PV system testbed is adopted to ob-
serve the LVRT dynamics. This model was developed
and posted by PSCAD [13]. The system topology is
shown in Figure 2. The solar farm consists of 100
PV arrays. Each unit generates a maximum power of
0.25 MW at the nominal irradiation of 1000W/m2
and nominal temperature of 28o. The MPPT, de-
tailed DC/DC boost converter, and detailed three-
phase switches are included, shown in Figure 1. The
system parameters are given in Table 4. The base volt-
age on the DC side is 1 kV. The DC voltage is con-
verted to 0.55 kV AC voltage through GSC.
4 Simulation results and discussions
4.1 Steady state voltage stability
In load flow analysis, PV solar power plants are usu-
ally integrated into the generator-type PV bus because
of their voltage control capability and due to the ac-
tive power generation [20]. On the other hand, they
are considered load buses after achieving their reac-
tive generation limits. Each PV solar power plant
has been characterized in the power system based on
the above hypothesis. The PV solar power plant is
synchronized with a grid by having inverters. They
do not provide voltage and frequency as a reference
by themselves when connected to the electrical in-
stallation. They measure the voltage and frequency
WSEAS TRANSACTIONS on POWER SYSTEMS
DOI: 10.37394/232016.2023.18.35
Abdelaziz Salah Saidi, Osama Ali Zemi,
Lina Alhmoud, Muhammad Umar Malik
E-ISSN: 2224-350X
343
Volume 18, 2023
Figure 2: IEEE 9- bus test systems [10].
Table 4: 25 MW PV solar power plant PSCAD testbed
parameters.
Description Parameters Value
Switching frequency 3 kHz (VSC) 5 kHz (DC-DC)
Power base Sb25 MW
Inverter power base S0
b250 kW
Inverter dc voltage base VDC,b 1 kV
PCC voltage base VP CC,b 0.55 kV
POC voltage base VP OC,b 33 kV
Power level PP OC,b 1 pu
System frequency fb60 Hz
LCL filter Lf ilter,Cfilter 0.32 mH, 54.80
µ
F
Damper Ldamp,Cdamp,Rdamp 1.60 mH, 27.40
µ
F, 7.65
Shunt capacitor BC10.2 pu
DC-link capacitor Cdc 10000
µ
F
PV LC filter LP V ,CP V 2.5 mH, 100
µ
F
Transformer impedance XT10.05 pu
Transmission line Xg,Rg0.45 pu, 0.05 pu
Current control loop Kpi,Kii (0.2, 20) pu
DC-link control loop Kpp,Kip (1,20) pu
VAC Control loop Kpv,Kiv (1,10) pu
PLL Kp,P LL,Ki,P LL (500,200) pu
at their connection point and deliver a power output
synchronized with this voltage and frequency of the
grid. Here, the inverters should be designed to have
no mismatches or instability in the electrical installa-
tion. In this work, the system voltage profile for peak
load conditions has been tested with and without con-
nection to a PV solar power plant. The characteristic
of the voltage profile at all IEEE 9-bus systems with
and without PV solar power plants are shown in Ta-
ble 5 and Figure 3. The bus voltage ranged from 0.995
to 1.028 pu at zero PV solar power plant connection
case. The voltage magnitude profile was improved
by integrating the PV solar power plant and injecting
the maximum power point tracking. It was observed
that the voltage magnitude was increased, but no over-
voltage was observed after integration for all busbars.
Remarkably, the grid voltage profile increased from
1.005 pu to 1.045 pu. In most of the buses in the sys-
tem, the voltage profile is within the 5% tolerance.
The terminal voltage phase angle at each connection
bus is measured in degrees for the system without and
with a PV solar power plant and presented in Table 5.
It can be perceived that the voltage angles of neigh-
boring buses are nearly identical, as demonstrated by
numerous references [6].
The base case results of load flow analysis of static
stability are given in Table 5 and Table 6, respectively.
The results show that MVAR losses are higher than
the MW losses. This is because the reactance val-
ues are greater than the resistive values, as shown in
Table 2. In the transmission lines, the active power
can transfer between the sending end and the receiv-
ing end in the transmission lines. The overloads on
highly loaded feeders and capacity release on these
feeders and substations are alleviated through the sig-
nificant penetration of PV solar power plants. There
is a minimization of total distribution power losses.
When connecting solar PV solar power plants, the
power losses moderately decrease compared with the
normal system power losses; thus, power losses ver-
sus the penetration rate of the solar PV system.
Figure 4, Figure 5, Figure 6, Figure 7, Figure 8,
Figure 9, Figure 10, Figure 11, Figure 12, and Fig-
ure 13 show the steady state analysis (base case) for
WSEAS TRANSACTIONS on POWER SYSTEMS
DOI: 10.37394/232016.2023.18.35
Abdelaziz Salah Saidi, Osama Ali Zemi,
Lina Alhmoud, Muhammad Umar Malik
E-ISSN: 2224-350X
344
Volume 18, 2023
Table 5: The busbar voltage (pu) for the IEEE 9-bus
system with & without PV power plant connected.
Bus Bus voltage(pu) Bus angle (o) Bus voltage (pu) Bus angle (o)
Bus 1 (swing) 1.036 4.1 1.045 5.1
Bus PV - - 1.032 -
Bus 2 1.02 8.5 1.032 11.0
Bus 3 1.02 4.9 1.029 6.3
Bus 4 1.021 -3.3 1.005 0.12
Bus 5 0.995 -5.0 1.012 -2.0
Bus 6 1.007 4.98 1.035 -0.12
Bus 7 1.022 -1.0 1.024 2.5
Bus 8 1.012 0.9 1.038 3.2
Bus 9 1.028 2.2 1.045 4.97
Table 6: The base case of load flow analysis for IEEE
9-bus system via. losses in transmission lines with &
without PV solar power plant connected.
From To Without PV With PV
Bus Bus Losses (MW) Losses (MVAR) Losses (MW) Losses (MVAR)
Bus 4 Bus 5 0.33 -15.94 0.3 -16.23
Bus 4 Bus 6 0.16 -15.458 0.09 -16.064
Bus 5 Bus 7 -2.19 0.643 1.98 5.382
Bus 7 Bus 8 0.51 -11.06 0.46 -12.6851
Bus 8 Bus 9 -0.08 21.148 -0.10 21.5601
Bus 9 Bus 6 1.52 4.4 1.14 -6.41
0
0.2
0.4
0.6
0.8
1
1.2
Bus 1 Bus
PV
Bus 2 Bus 3 Bus 4 Bus 5 Bus 6 Bus 7 Bus 8 Bus 9
Without PV 1.036 0 1.02 1.02 1.021 0.995 1.007 1.002 1.012 1.028
With PV 1.045 1.032 1.032 1.029 1.005 1.012 1.035 1.024 1.038 1.045
Bus voltage (pu)
Bus No.
Figure 3: Bus bar voltage for the system under study
with & without PV solar power plant.
the system under study. Figure 4 shows the active
power generation at bus, Figure 5 shows the active
power generation at bus 2 & bus 3. Figure 6 shows the
reactive power generation at bus 1, Figure 7 shows the
reactive power generation at bus 2 & bus 3, Figure 8
shows the bus voltage at all buses, Figure 9 shows the
active power at load bus 5 & bus 8, Figure 10 shows
the active power at load bus 6, Figure 11 shows the
reactive power at load buses 5 & bus 8, Figure 12
shows the reactive power at load bus 6, Figure 13
shows the bus angle at all buses. The dynamic volt-
age stability of the studied power system was exam-
ined by assessing the behavior of the voltage at the
buses during the normal conditions. The simulation
results show that the solutions of the dynamic power
system model converge to the equilibrium character-
ized by the nominal voltage as well as active and re-
active power generation and consumed. The results
indicate also that the system is stable with respect to
the same voltage, reactive and active power solved by
the load flow analysis in the previous section.
Figure 4: Active power generation at bus 1- base case
(MW).
Figure 5: Active power generation at bus 2 & bus 3-
base case (MW).
Figure 6: Reactive power generation at bus 1- base
case (MVAR).
4.2 Dynamic performance
4.2.1 PV power plant disconnection
A base case scenario of PV solar power plants con-
nected to bus 6 in the IEEE 9-bus system is analyzed
as shown in Figure 14. Here, the initial conditions
WSEAS TRANSACTIONS on POWER SYSTEMS
DOI: 10.37394/232016.2023.18.35
Abdelaziz Salah Saidi, Osama Ali Zemi,
Lina Alhmoud, Muhammad Umar Malik
E-ISSN: 2224-350X
345
Volume 18, 2023
Figure 7: Reactive power generation at bus 2 & bus
3- base case (MVAR).
Figure 8: Bus voltage (pu) at all buses- base case
(MW).
Figure 9: Active power at load bus 5 & bus 8 base
case (MW).
Figure 10: Active power at load bus 6- base case
(MW).
have been set for 100% power output of the PV nom-
inal power at standard test condition (STC) at 25C
cell temperature, 1000W/m2solar radiation, and air
mass of 1.5. Figure 15, Figure 16, Figure 17, Fig-
ure 18, Figure 19, Figure 20, Figure 21, Figure 22,
Figure 23, and Figure 24 show the dynamic perfor-
Figure 11: Reactive power at load buses 5 & bus 8-
base case (MVAR).
Figure 12: Reactive power at load bus 6- base case
(MW).
Figure 13: Bus angle at all buses-base case.
mance analysis for the system under study with the
PV solar power plant connected to bus 6. During
this base case scenario, the voltage response at all
buses converges to the equilibrium nominal per-unit
values with and without a PV solar power plant con-
nection. Figure 15 and Figure 16 show the reactive
power generation at the synchronous generator power
plant swing bus 1 and the solar PV generator bus 2
equals 60 MW and 30 MW, respectively. Figure 17
and Figure 18 show the reactive power generation at
the synchronous generator power plant swing bus 1
and the solar PV generator bus 2, respectively. Fig-
ure 19 shows the bus voltage at all buses, Figure 20
shows the active power at load bus 5 & bus 8, Fig-
ure 21 shows the active power at load bus 6, Figure 22
shows the reactive power at light load buses 5 & bus
8, Figure 23 the reactive power at buses 6, Figure 24
shows the bus angle at all buses. Thus, there is a slight
improvement in the voltage profile in the PV solar
WSEAS TRANSACTIONS on POWER SYSTEMS
DOI: 10.37394/232016.2023.18.35
Abdelaziz Salah Saidi, Osama Ali Zemi,
Lina Alhmoud, Muhammad Umar Malik
E-ISSN: 2224-350X
346
Volume 18, 2023
Figure 14: IEEE 9-Bus test systems with PV solar power plant penetration.
power plant integration as seen in Figure 19. There-
fore, the system is in a state of stability, and all system
variables do not exceed the permissible limits. It can
be observed in Figure 15 that after the PV solar power
plant is connected online to the system, the active and
reactive power is no longer provided by the swing bus
only. Both the swing bus and the PV solar power plant
bus are contributed as shown in Figures 16 and Fig-
ure 18, respectively. It can be observed that PV so-
lar power plants supply the most active and reactive
power generation. Thus, the swing bus, bus 2, and
bus 3 decreased their power capabilities, and the PV
solar power plant helps the grid with power support
and voltage regulation to the overall system.
Figure 15: Active power generation at bus 1 (MW)
with PV solar power plant connected.
4.2.2 System short-circuit
The third scenario investigates the transient responses
of the sudden loss of the PV solar power plant con-
nected to bus 6, and a symmetrical three-phase fault
Figure 16: Active power generation at bus 2 & bus 3
(MW) with PV solar power plant connected.
Figure 17: Reactive power generation at bus 1 (MW)
with PV solar power plant connected.
was injected into the most loaded bus 8. The fault was
initiated at 3 s and cleared at 3.2 s, as shown in Fig-
ure 25 and Figure 26. It created a severe drop in the
active power synchronous generating system at the
swing bus 1, bus 2, and bus 3, respectively. After 10
s, the generation stations reached 78 MW, 1.7 MW,
and 0.9 MW, respectively. Figure 27 and Figure 28
WSEAS TRANSACTIONS on POWER SYSTEMS
DOI: 10.37394/232016.2023.18.35
Abdelaziz Salah Saidi, Osama Ali Zemi,
Lina Alhmoud, Muhammad Umar Malik
E-ISSN: 2224-350X
347
Volume 18, 2023
Figure 18: Reactive power generation at bus 2 & bus
3 (MVAR) with PV solar power plant connected.
Figure 19: Voltage al all buses (pu) with PV solar
power plant connected.
Figure 20: Active power at light load buses 5 & bus
8 (MW) with PV solar power plant connected.
Figure 21: Active power at load bus 6- base case
(MW) with PV solar power plant connected.
illustrate the variation in reactive power generation.
The transient peaks of 100 MVAR, 1 MVAR, and 0.5
MVAR were detected at the swing bus and generator
buses 2 and 3. Later, the transitory was wiped off in
a short period. It was also observed that the active
power generation decreased, with the reactive power
Figure 22: Reactive power at light load buses 5 & bus
8 (MVAR) with PV solar power plant connected.
Figure 23: Reactive power at buses 6 (MVAR) with
PV solar power plant connected.
Figure 24: Buses angle with PV solar power plant
connected.
generation at buses 1, 2, and 3 reaching a transitory
peak of 4.12 pu. The voltage profile of the system’s
different buses is presented in Figure 29. A significant
voltage drop was observed at bus 8 and bus 7, where
the fault was injected. A declined voltage value of
0 p.u. was noted at the most loaded bus 8. Thus, an
overall voltage drop to 0.4 in the grid is recorded. The
changes in the real and reactive power values of load
buses 5 & 8 were recorded and shown in Figures 30
and Figure 31, where the real power can be seen to
have significantly dropped to 10 MW, 0.0 MW, and
0.1 MW, respectively. A severe oscillation in the re-
active power demand at bus 8, as shown in Figure 32,
reached 35 MVAR and damped within 1.2 sec. Reac-
tive power at buses 6 (MVAR) with 3-φSC at bas 8
and without PV solar power plant connected as shown
in Figure 33.
WSEAS TRANSACTIONS on POWER SYSTEMS
DOI: 10.37394/232016.2023.18.35
Abdelaziz Salah Saidi, Osama Ali Zemi,
Lina Alhmoud, Muhammad Umar Malik
E-ISSN: 2224-350X
348
Volume 18, 2023
Figure 25: Active power at bus 1 (MW) with 3-φSC
at bas 8 and without PV solar power plant connected.
Figure 26: Active power at bus 2 & bus 3 (MW) with
3-φSC at bas 8 and without PV solar power plant con-
nected.
Figure 27: Reactive power at bus 1 (MVAR) with 3-φ
SC at bas 8 and without PV solar power plant con-
nected.
Figure 28: Reactive power at bus 2 & bus 3 with 3-φ
SC at bas 8 and without PV solar power plant con-
nected.
4.2.3 Voltage dip faults at PV solar power plant
In this scenario, a three-phase short circuit was ap-
plied at t= 20 s and cleared in 120 ms. Figure 34
Figure 29: Voltage at all buses (pu) with 3-φSC at
bas 8 and without PV solar power plant connected.
Figure 30: Active power at load bus 5 & bus 8 (MW)
with 3-φSC at bas 8 and without PV solar power plant
connected.
Figure 31: Active power at load bus 6- base case
(MW) with 3-φSC at bas 8 and without PV solar
power plant connected.
Figure 32: Reactive power at light load buses 5 & bus
8 (MVAR) with 3-φSC at bas 8 and without PV solar
power plant connected.
shows the PV solar power plant bus voltage behav-
ior for all the terminal bus locations during the fault-
ride-through. Instantly after the occurrence of a fault,
WSEAS TRANSACTIONS on POWER SYSTEMS
DOI: 10.37394/232016.2023.18.35
Abdelaziz Salah Saidi, Osama Ali Zemi,
Lina Alhmoud, Muhammad Umar Malik
E-ISSN: 2224-350X
349
Volume 18, 2023
Figure 33: Reactive power at buses 6 (MVAR) with
3-φSC at bas 8 and without PV solar power plant con-
nected.
Figure 34: Voltage at all buses (pu) with 3-φSC at
bas 8 and without PV solar power plant connected.
the voltage at the PV bus drops from 1.0 p.u and at
buses 5 and 8, respectively, to 0.2 p.u and 0.0 p.u ac-
cording to the geographical distance of the respective
PV farm. During the fault rides through, this voltage
starts rising towards their rated values with an over-
shot in voltage at some buses: 5 and 8. These over-
shoots are because of the low capacity of those buses.
Immediately after the fault is cleared at 5.120 s, as the
PV farm begins a voltage regulation mode, the voltage
at the PV terminal starts to reach its rated values. As
demonstrated in Figures 35 and Figure 36, the active
power generation at the PV solar power plant, swing
bus 1, and generator buses 2 and 3 has experienced
a dip reaching down to 0.2 pu due to a three-phase
fault occurring at bus 8. Since a fast has protracted the
PV bus, continuously acting controller by the schema
of regulation. Thus, the voltage regulation at the PV
bus is guaranteed. Figure 37 and Figure 38 depict a
PV solar power plant bus’s reactive power production
pattern to provide voltage backing during the fault pe-
riod. It is observed that the PV bus has contributed
the most in supporting the system voltage regulation
because the PV bus is the geographically nearest gen-
erating bus to the faulted bus 8. The results also show
that the system is stable. Also, the power system has
a good transient performance with rapid recovery of
terminal voltage and reactive and active power during
and after the fault clearance.
Figure 39 shows the bus voltage at all buses, Fig-
ure 40 shows the active power at load bus 5 & bus 8,
Figure 35: Active power at bus 1 (MW) with 3-φSC
at bas 8 and PV solar power plant connected.
Figure 36: Active power at bus 2 & bus 3 (MW) with
3-φSC at bas 8 and PV solar power plant connected.
Figure 37: Reactive power at bus 1 (MVAR) with 3-φ
SC at bas 8 and PV solar power plant connected.
Figure 38: Reactive power at bus 2 & bus 3 with 3-φ
SC at bas 8 and PV solar power plant connected.
Figure 41 shows the active power at load bus 6, Fig-
ure 42 shows the reactive power at light load buses
5 & bus 8, Figure 43 the reactive power at buses 6,
Figure 44 shows the bus angle at all buses.
WSEAS TRANSACTIONS on POWER SYSTEMS
DOI: 10.37394/232016.2023.18.35
Abdelaziz Salah Saidi, Osama Ali Zemi,
Lina Alhmoud, Muhammad Umar Malik
E-ISSN: 2224-350X
350
Volume 18, 2023
Figure 39: Voltage at all buses (pu) with 3-φSC at
bas 8 and PV solar power plant connected.
Figure 40: Active power at load bus 5 & bus 8 (MW)
with 3-φSC at bas 8 and PV solar power plant con-
nected.
Figure 41: Active power at load bus 6- base case
(MW) with 3-φSC at bas 8 and PV solar power plant
connected.
Figure 42: Reactive power at light load buses 5 & bus
8 (MVAR) with 3-φSC at bas 8 and PV solar power
plant connected.
5 Conclusion
This paper helped to create a test beds for transient
stability study. The uniqueness of the proposed test
Figure 43: Reactive power at buses 6 (MVAR) with
3-φSC at bas 8 and without PV solar power plant con-
nected.
Figure 44: Voltage at all buses (pu) with 3-φSC at
bas 8 and PV solar power plant connected.
bed helped to validate the modeling of the IEEE 9-bus
and the performance of a PV solar power plant for a
variety of applications and validate the dynamic per-
formance of the system. It demonstrated how the pro-
posed test bed can be beneficial in investigating the
impact of integrating the PV solar power plant. These
scenarios helped in understanding the issues related to
the increase of penetration of PV solar power plants
to maximize electrical energy capacity, especially in
weak systems, and increase the security and reliability
of the grid as the PV solar system penetration grows.
Thus, investigation of voltage stability demonstrates
that the dynamic comportment of the voltage depends
strangely on the short circuit capability of the trans-
mission system at the bus of integration with the PV
station. The dynamic performance of the grid has pre-
sented compliance with voltage ride-through capabil-
ities that can be improved using a supplementary re-
active supply. The extra generation of PV power has
been found to considerably improve the voltage reg-
ulation, even in the case of over-voltages. Due to the
additional reactive power absorption capacity offered
by solar generators, a significant improvement in the
system voltage regulation capability has been found.
Due to the importance of the reactive power value ob-
tained at the common coupling point with the grid, the
reactive power contributions of SPV are taken into ac-
count. Abrupt disconnection of PV farms results in a
voltage drop of 6% of the nominal voltage. Bus 8 has
been mostly affected by this disruption, for which a
WSEAS TRANSACTIONS on POWER SYSTEMS
DOI: 10.37394/232016.2023.18.35
Abdelaziz Salah Saidi, Osama Ali Zemi,
Lina Alhmoud, Muhammad Umar Malik
E-ISSN: 2224-350X
351
Volume 18, 2023
secondary frequency regulation action is necessary.
Further research may be carried out to address
the following issues, such as developing detailed
inverter-based solar models and controls to study and
improve stability issues under fault conditions. Be-
sides, additional variations of the load model could
be considered. In particular, the mechanical torque
of the induction motor load can be modified to, e.g.,
quadratic or a combination of different torque charac-
teristics to form composite mechanical loads, which
would affect short-term voltage stability. The addi-
tional operating points in the test system should be
considered, e.g., PV systems that do not operate at
unity power factor. Moreover, higher PV penetra-
tion levels are also of interest. Moreover, the stud-
ied contingencies could be varied in terms of fault lo-
cation, fault impedance, fault type, or fault duration
to affect different PV systems, induction motors, and
synchronous generators in the test system. In contin-
uation to the presented study, an extension has been
intended to investigate the effects of different FACTS
devices and the effect of environment temperature and
irradiance on the dynamic voltage stability of the grid.
References:
[1] P. S. Kundur, Power System Stability And Con-
trol. McGraw-Hill, Inc, 2007.
[2] A. S. Saidi and M. I. Al-Rayif, “Impact of static
and dynamic load model on the low voltage
ride-through of the doubly-fed induction gener-
ator wind farm,” WSEAS Transactions on Power
Systems, vol. 12, pp. 1–10, 2017.
[3] K. Gunalan and C. Sharmeela, “A new control
strategy to enhance LVRT for doubly fed induc-
tion generator,” WSEAS Transactions on Power
Systems, vol. 10, pp. 135–144, 2015.
[4] S. A. Adegoke and Y. Sun, “Power system opti-
mization approach to mitigate voltage instability
issues: A review,” Cogent Engineering, vol. 10,
2023.
[5] A. G. Expósito and E. R. Ramos, “Augmented
rectangular load flow model,” IEEE Transac-
tions on Power Systems, vol. 17, pp. 271–276,
2002.
[6] A. S. Saidi, F. Alsharari, E. M. Ahmed, S. F.
Al-Gahtani, S. M. Irshad, and S. Alalwani, “In-
vestigating the impact of grid-tied photovoltaic
system in the Aljouf region, Saudi Arabia, us-
ing dynamic reactive power control,” Energies,
vol. 16, 2023.
[7] L. Zeng, H. D. Chiang, L. S. Neves, and L. F. C.
Alberto, “On the accuracy of power flow and
load margin calculation caused by incorrect log-
ical PV/PQ switching: Analytics and improved
methods,” International Journal of Electrical
Power and Energy Systems, vol. 147, 2023.
[8] J. Machowski, Z. Lubosny, J. Bialek, and
J. Bumby, Power System Dynamics: Stability
and Control, 3rd Edition. Wiley, 2020.
[9] J. Shair, H. Li, J. Hu, and X. Xie, “Power sys-
tem stability issues, classifications and research
prospects in the context of high-penetration
of renewables and power electronics,” Renew-
able and Sustainable Energy Reviews, vol. 145,
2021.
[10] Illinois Center for a Smarter Electric Grid,
“Wscc 9-bus system.” https://icseg.iti.
illinois.edu/wscc-9-bus-system/, Last
accessed on 22-12-2023.
[11] A. Gupta and R. K. Pachar, “A hybrid signal
processing technique for identification and cate-
gorization of faults in IEEE-9 bus system,” Ad-
vanced Engineering Forum, vol. 49, pp. 43–55,
2023.
[12] R. O. Olarewaju, A. S. Ogunjuyigbe, T. R. Ayo-
dele, T. C. Mosetlhe, and A. A. Yusuff, “Assess-
ing the voltage stability of power system in the
presence of increasing solar PV penetration,” in
IEEE AFRICON 2023, Nairobi, Kenya, Septem-
ber 20-22, 2023, pp. 1–6, IEEE, 2023.
[13] Manitoba Hydro International Ltd., “Sim-
ple solar farm model written for PSCAD
X4 version 4.6.3,” 2019. https:
//www.pscad.com/knowledge-base/
download/simplesolarfarm2019.pdf,
Last accessed on 22-12-2023.
[14] N. U. Putri, F. Rossi, A. Jayadi, J. P. Sembir-
ing, and H. Maulana, “Analysis of frequency
stability with SCES’s type of virtual inertia con-
trol for the IEEE 9 bus system,” in 2021 Inter-
national Conference on Computer Science, In-
formation Technology, and Electrical Engineer-
ing, ICOMITEE 2021, pp. 191–196, Institute of
Electrical and Electronics Engineers Inc., 2021.
[15] N. Anwar, H. F. Khan, M. F. Ullah, and A. Hanif,
“Transient stability analysis of the IEEE-9 bus
system under multiple contingencies,” Engi-
neering, Technology and Applied Science Re-
search, vol. 10, pp. 5925–5932, 2020.
[16] K. Loji, I. E. Davidson, and R. Tiako, “Volt-
age profile and power losses analysis on a mod-
ified IEEE 9-bus system with PV penetration
WSEAS TRANSACTIONS on POWER SYSTEMS
DOI: 10.37394/232016.2023.18.35
Abdelaziz Salah Saidi, Osama Ali Zemi,
Lina Alhmoud, Muhammad Umar Malik
E-ISSN: 2224-350X
352
Volume 18, 2023
at the distribution ends,” in Proceedings - 2019
Southern African Universities Power Engineer-
ing Conference/Robotics and Mechatronics/Pat-
tern Recognition Association of South Africa,
SAUPEC/RobMech/PRASA 2019, pp. 703–708,
Institute of Electrical and Electronics Engineers
Inc., 2019.
[17] O. Anaya-Lara and E. Acha, “Modeling
and analysis of custom power systems by
PSCAD/EMTDC,” IEEE Transactions on
Power Delivery, vol. 17, pp. 266–272, 2002.
[18] B. Gorgan, S. Busoi, G. Tanasescu, and P. V.
Notingher, “PV plant modeling for power sys-
tem integration using PSCAD software,” in
2015 9th International Symposium on Advanced
Topics in Electrical Engineering, ATEE 2015,
pp. 753–758, Institute of Electrical and Elec-
tronics Engineers Inc., 2015.
[19] L. Alhmoud, “Why does the PV solar power
plant operate ineffectively?,” Energies, vol. 16,
2023.
[20] S. Karmakar and B. Singh, “Multi-MPPT 72-
pulse VSC based high-power grid interfaced so-
lar PV plant with distributed DC-coupled battery
energy storage,” IEEE Transactions on Energy
Conversion, 2023.
Contribution of Individual Authors to the
Creation of a Scientific Article (Ghostwriting
Policy)
Abdelaziz Salah Saidi: Formal analysis, In-
vestigation, Methodology, Software, Super-
vision, Visualization, Writing original draft.
Osama Ali Zemi: Formal analysis, Investigation,
Methodology, Software, Supervision, Validation.
Lina Alhmoud: Methodology, Project ad-
ministration, Supervision, Validation, Vi-
sualization, Writing review & editing.
Muhammad Umar Malik: Data cura-
tion, Formal analysis, Methodology,
Resources, Software, Supervision.
Sources of Funding for Research Presented in a
Scientific Article or Scientific Article Itself
Report potential sources of funding if there is any
No funding was received for conducting this study.
No Conflicts of Interest
The authors have no conflicts of interest to
declare that are relevant to the content of this
article.
Creative Commons Attribution License 4.0
(Attribution 4.0 International , CC BY 4.0)
This article is published under the terms of the
Creative Commons Attribution License 4.0
WSEAS TRANSACTIONS on POWER SYSTEMS
DOI: 10.37394/232016.2023.18.35
Abdelaziz Salah Saidi, Osama Ali Zemi,
Lina Alhmoud, Muhammad Umar Malik
E-ISSN: 2224-350X
353
Volume 18, 2023