ANFIS-Fuzzy Logic-based Hybrid DFIG and PMSG Grid
Connected System with TCSC
K.KARTHI, A. RAMKUMAR
Dept of EEE., Kalasalingam Academy of Research and Education (KARE), Srivillliputhu,
Tamilnadu, INDIA
Abstract: Variable-speed wind turbines might provide green electricity. Grid operators' grid
regulations require wind turbines to recover from grid disruptions and help maintain electricity
networks. Having wind turbines equipped with fault current limiters (FCLs) may ensure their
continued functioning in the event of a power loss. In this piece, we will talk about how to improve
the two most common types of variable-speed wind turbines: the Doubly Fed Induction Generator
(DFIG) and the Permanent Magnet Synchronous Generator (PMSG). Both wind generators were
evaluated using the Thyristor Controlled Series Compensator (TCSC) with ANFIS and Fuzzy Logic.
It is important to understand the dynamic behavior of wind turbines, hence models of their FCLs were
built for steady state and grid disruptions. Power interruptions switched the FCLs in both wind
turbines utilising grid voltage variation. Both wind turbines underwent a no-control FCL scenario.
Both wind turbines' FCLs were measured and compared under load from a severe three-phase to
ground failure at their terminals. Both wind turbines were operated under similar circumstances to
examine FCL control tactics during power interruptions.
Keywords: ANFIS, Fuzzy Logic, Total Harmonic Distortions, Wind Energy conversion system, DFIG, and
PMSG Control.
Received: February 23, 2023. Revised: November 15, 2023. Accepted: December 15, 2023. Published: January 30, 2024.
1. Introduction
It is crucial to acquire new methods of
power grid stabilization for smooth operation
[1,2] since wind energy penetration into existing
power grids develops day by day, with an
average projection of 75 GW per year during the
2021-2026 timeframe. Wind farms are an
emerging industry that requires sophisticated
voltage and frequency control to meet their grid
requirements. As a result of the broad operating
window afforded by variable-speed wind turbine
technology [3], these machines are more
common. The two most common types of
variable-speed wind turbines used in current
wind farms are the DFIG and the PMSG.
The development of power electronics
and drives in control mechanisms has greatly
facilitated the transition of wind turbines from
fixed speed to variable speed technology [4,5].
Advantages of fixed-speed wind turbines
include their simplicity, durability, affordability,
and minimal maintenance requirements.
However, there are significant challenges
associated with this type of wind turbine, which
prevent it from being widely used in wind
energy applications. These include a lack of
control over voltage and frequency and the need
for substantial reactive power during grid
disturbances to survive air-gap flux recovery.
Thus, variable-speed wind turbines are
employed in the building of contemporary wind
farms because of their high energy capture
efficiency, effective voltage management, and
lower mechanical drive train stress [6]. Both the
DFIG and PMSG wind turbine technologies use
a series connections of power converters. The
PMSG's high initial cost is owing to its full-rated
power converters, whereas the DFIG's gearbox
system has a lower power converter rating of 20-
30 percent. Active and reactive power
management is simplified by the DFIG
technology's architecture, which links the Rotor
Side Converter (RSC), also known as the
Machine Side Converter (MSC), and the Stator
Side Converter (SSC), also known as the Grid
Side Converter (GSC), through the DC-link
voltage.
These wind turbines have a great pitch
adjustment system that allows them to recover
their voltage after grid disturbances [9,10] and
operate in a broad range to maximize energy
absorption [7,8]. However, the back-to-back
power converter in a PMSG wind turbine is fully
rated, whereas that in a DFIG wind turbine is
only rated at 50%. This kind of wind turbine is
thus more likely to provide optimal adaptability
International Journal of Electrical Engineering and Computer Science
DOI: 10.37394/232027.2024.6.6
K. Karthi, A. Ramkumar
E-ISSN: 2769-2507
51
Volume 6, 2024
and superior control over active and reactive
power. However, the PMSG's prohibitive
upfront cost is a major drawback. Numerous
control schemes, such as FCLs in DFIG wind
turbines [11–14], reactive power compensation,
crowbar, and DC chopper [15–16], and sliding
mode control for Maximum Power Point
Tracking (MPPT) [17–18], have previously
been reported in the literature. Methods for wind
energy conversion were provided in [22] and the
Fault Ride Through (FRT) assessment of a
DFIG wind turbine was conducted using several
control topologies in [19-21].
However, in [23,24], the DC-link voltage
was maintained at its limit during a grid failure,
and the maximum current and MPPT power
converters for the PMSG wind turbine were
investigated. [25] bolstered the performance of
the PMSG turbine with the aid of a
superconducting fault current limiter (SFCL)
control mechanism. This study investigated the
permanency problems of DFIG and PMSG wind
turbines and how their augmentation evaluations
compare to existing FCLs. Similar studies can be
found in [26-28]. Both types of wind generators'
control topologies and wind turbine-modeling
elements were detailed. Both wind turbines had
a severe bolted three-line-to-ground failure with
no FCL control or augmentation strategy to test
the controllers' robustness. The mathematical
dynamics of inserting SDBR, BFCL, and
CBFCL at the stator of both wind turbines under
similar operating circumstances were also
supplied for fair comparison. Each wind turbine
system used an SDBR with the same effective
size and the same BFCL and CBFCL
parameters. During a grid failure, the grid
voltage was utilized as the switching signal.
Only a small number of articles in the scholarly
literature investigate the presence of these FCLs
in both types of wind turbines. FRT
enhancement of both wind turbines has only
been briefly touched on in a few of the
aforementioned papers.
2. The System Model
2.1 Modelling of DFIG
To simplify, the DFIG may be seen as a
conventional induction generator with a nonzero
rotor [8]. Both the rotor converter, which
regulates the rotational speed of the generator,
and the grid converter, which injects reactive
energy into the grid, make up the power
converter of a wind turbine. The actual and
reactive power components of the grid-side
converter(GSC) are shown in Figure 1.
According to [9], in a synchronously rotating
direct-quadrature (d-q) reference frame, the
dynamic equation of a three-phase DFIG's
voltages and flux connections may be written as
(1) through (8):
2.2. DFIG Control Model
and reactive power is regulated by the
RSC controller, while DC-link voltage and
reactive power injection into the grid are
managed by the grid-side converter (GSC)
controller. In a Graetz bridge configuration,
snubber resistance and capacitance are added to
the RS of a three-phase IGBT-diode rectifier to
dampen vibrations. The DC bus capacitor
voltage is controlled by the grid-side converter
[11]. By adjusting the pitch angle, we can
determine how much energy can be harvested in
strong winds. A torque controller is used in the
control system to maintain a consistent velocity.
The reactive power of the wind turbine is
likewise kept at 0 MVAR. The control
equations, as seen from the rotor, might be
represented in the form of Figure 2.
2.3 Grid Side Controller
Maintaining a fixed DC-link voltage
regardless of the magnitude or direction of the
rotor's power flow [12] is the primary goal of the
GSC. To accomplish this, we use the hysteresis
current control approach shown in Figure 2,
which uses a reference frame that is co-linear
with the stator voltage position. The reactive
power and the DC-link voltage between the
converter and the grid may thus be
independently controlled.
In a voltage vector-oriented reference
frame, the current regulates the DC-link voltage.
Therefore, as illustrated in Figure 2, a reference
current value is calculated by tuning a PI
controller using the DC-link voltage error e and
the error variation.
International Journal of Electrical Engineering and Computer Science
DOI: 10.37394/232027.2024.6.6
K. Karthi, A. Ramkumar
E-ISSN: 2769-2507
52
Volume 6, 2024
Fig. 1: General block diagram of the proposed system
Fig. 2: Mathematical modeling of Hybrid system
International Journal of Electrical Engineering and Computer Science
DOI: 10.37394/232027.2024.6.6
K. Karthi, A. Ramkumar
E-ISSN: 2769-2507
53
Volume 6, 2024
3. Thyristor Controlled Series
Compensator
The benefits of series capacitors over
shunt capacitors are substantial. The reactive
power of a series capacitor is proportional to the
square of the line current, whereas the reactive
power of an inductor-capacitor is related to the
square of the short circuit in a bus circuit. The
reactive power rating of a shunt capacitor
typically has to be three to six times higher than
that of a series capacitor to provide the same
system advantages as those of a series capacitor.
Additionally, shunt capacitors often need to be
linked in the middle, while series capacitors have
no such need.
3.1 Operation of TCSC controller.
Continuous control of power on the AC
line is made possible by a TCSC, a series-
regulated capacitive reactance. Analyzing the
operation of a TCSC may be reduced to a few
simple steps by considering the effects of a
variable induction linked in series with a constant
capacitor, as seen in Fig. 3. This combination's
equivalent impedance, Zeq, may be written as
 󰇡
󰇢󰇛󰇜 

 (1)
If  󰇛
󰇜  󰇛
󰇜 , Since
the FC's reactance is below the along a variable
reactor's, the resulting reactance is adjustable
capacitance. If  󰇛
󰇜 , Inadequate
conditions include the development of a
resonance leading to infinite capacitive
impedance. If  󰇛
󰇜 , Therefore the
inductance provided by the combination is greater
than that of a fixed inductor. In this case, the
TCSC is operating in its inductive micrometre
mode.
Analysis of a TCSC behaves similarly to that of
an LC parallel combination when the voltage and
current in the circuit are pure sinusoids. In
contrast, thyristor switching causes non-
sinusoidal voltage and current in a TCSC's fuel
cell (FC) and thyristor-controlled reactor (TCR).
Further sections elaborate on how TCSC operates
in detail.
The DFIG and PMSG generator data tables 1
and 2 each include information for one turbine
used in simulations.
TABLE 1: The Design Parameters Of DFIG
Generator Data for one Turbine
Nominal Electrical Power
1.5MVA
Stator Resistance, Rs
0.23p.u.
Rotor Resistance, Rr
0.016 p.u.
Stator Inductance, Ls
0.18 p.u.
Rotor Inductance, Lr
0.16 p.u.
Magnetizing inductance, Lm
2.9 p.u.
Inertia Constant, H
0.685
Pole Pair, p
3
TABLE 2: The Design Parameters Of PMSG
Generator Data for one Turbine
1.5MVA
0.00 p.u.
1150
48
2.9 p.u.
0.005
3
4. Discussion of the Findings
The PMSG rating system is identical to
the DFIG rating system. Figure 4 depicts the
Simulink equivalent circuit diagram for this
system. To assess the performance of Hybrid
PMSG and DFIG in terms of output powers
(P&Q), voltages and current, THD, and dynamic
responses with ANFIS and with Fuzzy based
TCSC, a failure (time = 1 Sec to 1.75 Sec) is
simulated for both machine side bus (B575). The
active and reactive powers are given in Figs. 5,
6, and 7, respectively, for comparison. The
oscillations in DFIG+PMSG with ANFIS-based
TCSC active power are demonstrated in Figure
10 to be substantially lower than those in
DFIG+PMSG with Fuzzy based TCSC during
fault. DFIG and PMSG with ANFIS based
TCSC attain steady-state values after 3.5
seconds, however, with Fuzzy based TCSC, they
continue to fluctuate even after 5 seconds. In
addition, Figure 11 depicts the reaction of DFIG
and PMSG reactive power with ANFIS based
and with Fuzzy based TCSC. Reactive power
regulation with ANFIS based TCSC at zero
International Journal of Electrical Engineering and Computer Science
DOI: 10.37394/232027.2024.6.6
K. Karthi, A. Ramkumar
E-ISSN: 2769-2507
54
Volume 6, 2024
MVAR is much superior than that with Fuzzy
based TCSC during a malfunction. During a
fault, the reactive power deviation from zero
MVAR is substantially lower with ANFIS based
TCSC than with Fuzzy based TCSC, but once
the fault is cleared, the reactive power of with
Fuzzy based TCSC recovers to zero in a much
shorter time than with ANFIS based TCSC. As
a result, if a system requires that reactive power
be controlled at zero MVAR for an extended
period and abrupt large deviations are permitted,
then a system with Fuzzy based TCSC may be a
preferable solution. Still, if a system requires
that reactive power not move too much from
zero MVAR, TCSC may be a preferable
alternative. Figure 8 shows a voltage
comparison with ANFIS based and with Fuzzy
based TCSC. During the fault, the voltage of
DFIG and PMSG with ANFIS based TCSC
oscillates roughly 10% more than the voltage of
DFIG and PMSG with Fuzzy based TCSC
owing to flux oscillations necessary to supply
the reactive power. This is because speed is
inversely related to flux. Furthermore, DFIG and
PMSG with ANFIS based TCSC have greater
inertia due to their heavier weight than DFIG
and PMSG with Fuzzy based TCSC. The
voltage and current of DFIG and PMSG with
ANFIS based TCSC achieve steady-state in a
much shorter time than DFIG and PMSG with
Fuzzy based TCSC. DFIG and PMSG with
ANFIS based TCSC achieve a steady-state value
at t = 2.5 seconds, but DFIG and PMSG with
Fuzzy based TCSC fluctuate even at t = 4.5
seconds. As a result, if the voltage and current
control are more important, DFIG and PMSG
with ANFIS based TCSC should be utilized;
otherwise, DFIG and PMSG with Fuzzy based
TCSC might be employed. THDs of voltages of
DFIG and PMSG with Fuzzy based TCSC and
DFIG and PMSG with ANFIS based TCSC are
shown in Figs. 8 and 9, respectively, owing to
fault. They demonstrate that harmonic distortion
is lower in DFIG and PMSG with ANFIS based
TCSC than in DFIG and PMSG with Fuzzy
based TCSC; hence, power quality is optimum
when DFIG and PMSG with ANFIS based
TCSC are used with ANFIS based an innovative
power electronic interface. As a result, it is
determined that DFIG and PMSG with ANFIS
based TCSC are more effective as wind turbine
generators than DFIG and PMSG with Fuzzy
based TCSC, and that unconventional power
electronic interfaces are more effective as
interfaces than standard power electronic
interfaces
Fig. 3: The Simulink equivalent circuit diagram of DFIG and PMSG with ANFIS based TCSC
system
International Journal of Electrical Engineering and Computer Science
DOI: 10.37394/232027.2024.6.6
K. Karthi, A. Ramkumar
E-ISSN: 2769-2507
55
Volume 6, 2024
Fig. 4: Simulink diagram of DFIG system
Fig. 5: Simulink diagram of PMSG with machine side and grid side controller
International Journal of Electrical Engineering and Computer Science
DOI: 10.37394/232027.2024.6.6
K. Karthi, A. Ramkumar
E-ISSN: 2769-2507
56
Volume 6, 2024
Fig. 6: Simlink diagram of TCSC controller
(a)
(b)
Fig. 7: Grid Side Output Voltage Fault created from 1 Sec to 1.75 Sec (a) DFIG and PMSG with
Fuzzy based TCSC (b) DFIG and PMSG with ANFIS based TCSC
International Journal of Electrical Engineering and Computer Science
DOI: 10.37394/232027.2024.6.6
K. Karthi, A. Ramkumar
E-ISSN: 2769-2507
57
Volume 6, 2024
(a)
(b)
Fig. 8: Grid Side Output Current during the fault condition (Fault created from 1 Sec to 1.75 Sec) (a)
with ANFIS based TCSC (b) with ANFIS based Fuzzy based TCSC
(a)
International Journal of Electrical Engineering and Computer Science
DOI: 10.37394/232027.2024.6.6
K. Karthi, A. Ramkumar
E-ISSN: 2769-2507
58
Volume 6, 2024
(b)
Fig. 9: Real power during the fault condition (Fault created from 1 Sec to 1.75 Sec) (a)with ANFIS
based TCSC (b) with Fuzzy based TCSC
(a)
Fig. 10: Reactive power during the fault condition (Fault created from 1 Sec to 1.75 Sec) (a) with
ANFIS based TCSC (b) with Fuzzy based TCSC
International Journal of Electrical Engineering and Computer Science
DOI: 10.37394/232027.2024.6.6
K. Karthi, A. Ramkumar
E-ISSN: 2769-2507
59
Volume 6, 2024
(a)
(b)
Fig. 11: DC link voltage with ANFIS based TCSC (b) with Fuzzy based TCSC
Fig. 12: Gate pulse
(a)
(b)
Fig. 13: THD Values (a) with Fuzzy based TCSC (b) with ANFIS based TCSC
International Journal of Electrical Engineering and Computer Science
DOI: 10.37394/232027.2024.6.6
K. Karthi, A. Ramkumar
E-ISSN: 2769-2507
60
Volume 6, 2024
Fig. 14: Fuzzy logic rule viewers
(a)
(b)
(c)
Fig. 15: ANFIS based output (a) Surface
Window (b) ANFIS Designer Window (c)
ANFIS Structure Window
5. Conclusion
As a consequence, DFIG and PMSG with
ANFIS based TCSC are more effective wind
turbine generators than those with FUzzy based,
and unconventional power electronic interface is
more effective than standard power electronic
interface. The comparison may be summed up
by noting that during a fault, DFIG and PMSG
with FUzzy based TCSC both use more reactive
power than DFIG and PMSG with ANFIS based
TCSC consume under the same circumstances,
even after the improvement. The modifications
International Journal of Electrical Engineering and Computer Science
DOI: 10.37394/232027.2024.6.6
K. Karthi, A. Ramkumar
E-ISSN: 2769-2507
61
Volume 6, 2024
made to the DFIG and PMSG with Fuzzy based
TCSC control assist in the oscillation reduction
part of the machine's dynamic behavior. It takes
far longer for DFIG and PMSG with Fuzzy
based TCSC to recover their permanence than it
does for DFIG and PMSG with ANFIS based
TCSC, which implies that DFIG and PMSG
with ANFIS based TCSC are more dependable
than DFIG. On the other hand, the performance
of the DFIG and PMSG with ANFIS based
TCSC wind turbine was improved utilizing the
TCSC with 9% overshoot and 2.35 s settling
time for the actual and reactive power. The THD
values were with ANFIS based TCSC at 1.67%
with Fuzzy based TCSC at 28.35%. Moreover, a
quicker settling time was also seen employing
the TCSC for DFIG and PMSG. Except for the
terminal grid voltage variable, the ANFIS based
TCSC improved the performance of the DFIG
and PMSG. To achieve optimal fault ride-
through performance for a given application, it
is advised to couple TCSC-based variable speed
wind turbines with the DFIG and PMSG.
References
[1] Wind-Fuels and Technologies, International
Energy Agency. 2021. Available online:
https://www.iea.org.
[2] Nduwamungu, A. Ntagwirumugara, E. Mulolani,
F. Bashir, W., " Fault Ride through Capability
Analysis (FRT) in Wind Power Plants with
Doubly Fed Induction Generators for Smart Grid
Technologies," Energies vol. 13, pp. 42-60,2020.
[3] Sitharthan, R. Karthikeyan, M. Sundar, D.S.
Rajasekaran, S. , "Adaptive hybrid intelligent
MPPT controller to approximate effectual wind
speed and optimal rotor speed of variable speed
wind turbine," ISA Transaction, vol. 96, pp. 479
489,2020.
[4] Okedu, K.E. Muyeen, S.M. Takahashi, R.
Tamura, J., " Protection schemes for DFIG
considering rotor current and DC-link voltage," In
Proceedings of the 24th IEEE-ICEMS
International Conference on Electrical Machines
and System, Beijing, China, pp. 1–6, 20–23
August 2011.
[5] Ouyang, J. Tang, T. Yao, J. Li, M., "Active
Voltage Control for DFIG-Based Wind Farm
Integrated Power System by Coordinating Active
and Reactive Powers under Wind Speed
Variations," IEEE Transaction Energy Convers,
vol. 34, pp. 1504–1511,2019.
[6] Okedu, K.E., " Introductory Chapter of the book
Power System Permanency," INTECH: Horwich,
UK, pp. 1–10,2019.
[7] Shao, H. Li, Z. Zhou, D. Sun, S. Guo, L. Rao, F.,
"Permanency Enhancement and Direct Speed
Control of DFIG Inertia Emulation Control
Strategy," IEEE Access, vol. 7, pp. 120089
120105,2019.
[8] He, X. Fang, X. Yu, J., " Distributed Energy
Management Strategy for Reaching Cost-Driven
Optimal Operation Integrated with Wind
Forecasting in Multimicro grids System," IEEE
Transaction System Man Cyber. System, vol.49,
pp. 1643–1651,2019.
[9] Qazi, H.W. Wall, P. Escudero, M.V. Carville, C.
Cunniffe, N. Sullivan, J.O., "Impacts of Fault
Ride Through Behavior of Wind Farms on a Low
Inertia System," IEEE Transaction Power
System, vol. 28, no. 1, 2020.
[10] Chunli, L. Zefu, T. Huang, Q. Nie, W. Yao,
J., "Lifetime Evaluation of IGBT Module in
DFIG Considering Wind Turbulence and
Nonlinear Damage Accumulation Effect," In
Proceedings of the 2019 IEEE 2nd International
Conference on Automation, Electronics and
Electrical Engineering (AUTEEE), Shenyang,
China, pp. 22–24, November 2019.
[11] Okedu, K.E. Muyeen, S.M. Takahashi, R.
Tamura, J., " Use of Supplementary Rotor Current
Control in DFIG to Augment Fault Ride Through
of Wind Farm as per Grid Requirement," In
Proceedings of the 37th Annual Conference of
IEEE Industrial Electronics Society (IECON
2011), Melbourne, Australia, pp.7–10, November
2011.
[12] Okedu, K.E. Muyeen, S.M. Takahashi, R.
Tamura, J., " Improvement of Fault Ride Through
Capability of Wind Farm using DFIG
Considering SDBR," In Proceedings of the14th
European Conference of Power Electronics EPE,
Birmingham, UK, pp. 1–10,2011.
[13] Okedu, K.E., "Enhancing DFIG Wind
Turbine during Three-phase Fault Using Parallel
Interleaved Converters and Dynamic Resistor,"
IET Renewable Power Generation, vol. 10, pp.
1211–1219,2016.
[14] Okedu, K.E. Muyeen, S.M. Takahashi, R.
Tamura, J., " Participation of FACTS in
Stabilizing DFIG with Crowbar during Grid Fault
Based on Grid Codes," In Proceedings of the 6th
IEEE-GCC Conference and Exhibition, Dubai,
UAE, pp. 365–368, 2011.
[15] Boujoudi, B. Kheddioui, E. Machkour, N.
Achalhi, A. Bezza, M., " Comparative study
between different types of control of the wind
turbine in case of voltage dips," In Proceedings of
International Journal of Electrical Engineering and Computer Science
DOI: 10.37394/232027.2024.6.6
K. Karthi, A. Ramkumar
E-ISSN: 2769-2507
62
Volume 6, 2024
the 2018 Renewable Energies, Power Systems &
Green Inclusive Economy (REPS-GIE),
Casablanca, Morocco, pp. 1–5, 2018.
[16] Okedu, K.E. Muyeen, S.M. Takahashi, R.
Tamura, J., "Comparative Study between Two
Protection Schemes for DFIG-based Wind
Generator," In Proceedings of the 23rd IEEE-
ICEMS (International Conference on Electrical
Machines and Systems), Seoul, Korea, pp. 62–67,
2010.
[17] Okedu, K.E. Muyeen, S.M. Takahashi, R.
Tamura, J., "Stabilization of wind farms by
DFIG-based variable speed wind generators," In
Proceedings of the International Conference of
Electrical Machines and Systems (ICEMS),
Seoul, Korea, pp. 464–469, 2010.
[18] Bekakra, Y. Attous, D.B., "Sliding Mode
Controls of Active and Reactive Power of a DFIG
with MPPT for Variable Speed Wind Energy
Conversion," Australian Journal Basic Applied.
Science., vol. 5, pp.2274–2286, 2011.
[19] Ali, D.M. Jemli, K. Jemli, M. Gossa, M.,
"Doubly Fed Induction Generator, with Crowbar
System under Micro-Interruptions Fault," Int. J.
Electr. Eng. Inform., vol. 2, pp. 216–231, 2010.
[20] Suthar, D.B., "Wind Energy Integration for
DFIG Based Wind Turbine Fault Ride Through,"
Indian Journal Appl. Res. vol. 4, pp, 216–220,
2014.
[21] Lamchich, M.T. Lachguer, N., "Matlab,
Simulink as Simulation Tool for Wind Generation
Systems Based on Doubly Fed Induction
Machines," In MATLAB—A Fundamental Tool
for Scientific Computing and Engineering
Applications Chapter 7 INTECH Publishing:
Horwich, UK, vol. 2, pp. 139160, 2012.
[22] Noubrik, A. Chrifi-Alaoui, L. Bussy, P.
Benchaib, A., "Analysis and Simulation of a
1.5MVA Doubly Fed Wind Power in Matlab Sim
PowerSystems using Crowbar during Power
Systems Disturbances," In Proceedings of the
IEEE-2011 International Conference on
Communications, Computing and Control
Applications (CCCA), Hammamet, Tunisia, pp.
3–5, March 2011.
[23] Nasiri, M. Mohammadi, R., "Peak current
limitation for grid-side inverter by limited active
power in PMSG-based wind turbines during
different grid faults," IEEE Transaction Sustain.
Energy, vol. 8, pp. 3–12, 2018.
[24] Gencer, A., "Analysis and control of fault
ride through capability improvement PMSG
based on WECS using active crowbar system
during different fault conditions," Elektron.
Elektrotech, vol. 24, pp.64–69, 2018.
[25] Yehia, D.M. Mansour, D.A. Yuan, W.,
"Fault ride-through enhancement of PMSG wind
turbines with DC microgrids using resistive-type
SFCL," IEEE Transaction Applied Supercond.
vol. 28, pp,15, 2018.
[26] M. Ragab, H. A. Abdushkour, A. F. Nahhas
and W. H. Aljedaibi, "Deer hunting optimization
with deep learning model for lung cancer
classification," Computers, Materials &
Continua, vol. 73, no.1, pp. 533–546, 2022.
[27] X. R. Zhang, W. F. Zhang, W. Sun, X. M.
Sun and S. K. Jha, "A robust 3-D medical
watermarking based on wavelet transform for
data protection," Computer Systems Science &
Engineering, vol. 41, no. 3, pp. 1043–1056, 2022.
[28] Y. Y. Ghadi, I. Akhter, S. A. Alsuhibany, T.
A. Shloul, A. Jalal, et al., "Multiple events
detection using context-intelligence features,"
Intelligent Automation & Soft Computing, vol. 34,
no.3, pp. 1455–1471, 2022.
Contribution of Individual Authors to the
Creation of a Scientific Article (Ghostwriting
Policy)
The authors equally contributed in the present
research, at all stages from the formulation of the
problem to the final findings and solution.
Sources of Funding for Research Presented in a
Scientific Article or Scientific Article Itself
No funding was received for conducting this study.
Conflict of Interest
The authors have no conflicts of interest to declare
that are relevant to the content of this article.
Creative Commons Attribution License 4.0
(Attribution 4.0 International, CC BY 4.0)
This article is published under the terms of the
Creative Commons Attribution License 4.0
https://creativecommons.org/licenses/by/4.0/deed.en
_US
International Journal of Electrical Engineering and Computer Science
DOI: 10.37394/232027.2024.6.6
K. Karthi, A. Ramkumar
E-ISSN: 2769-2507
63
Volume 6, 2024