Experience in the Development of the Sine-Wave Filter for High-Power
Variable Voltage Variable Frequency Drive with Medium Voltage
Induction Motor
MIKHAIL PUSTOVETOV
Department of Electrical and Electronics Engineering,
Don State Technical University,
344000, Rostov region, Rostov-on-Don, Gagarin sq., 1
RUSSIA
Abstract: - The relevance of the work reflects the increased use in practice of variable frequency electric drive
additional options, which include sine-wave filter. The main aim of the study: is to develop guidelines for
choosing the parameters of the sine-wave filters and the correct selection of the elements in the current;
consider the phenomena occurring when the capacity is connected to terminals of the load with an induction
motor, such as: reactive power compensation and overcompensation, self-excitation. The methods used in the
study: test on a real process plant; and computer simulation of an electromechanical system with a
semiconductor converter based on a combination of circuit and operational principles for preparing the model.
The results: some of the results of experience in the design and testing of the sine-wave filter for high-power
variable voltage variable frequency drive with medium voltage induction motor with scalar control are
described. The comparative results of the computer simulation of processes at different sets of the sine-wave
filter and converter parameters are presented. Some recommendations for sine-wave filter design are suggested.
Key-Words: - frequency converter, pulse-width modulation of voltage, sine-wave filter, induction motor,
capacitance, reactive power, self-excitation, current.
Received: May 8, 2024. Revised: September 11, 2024. Accepted: November 10, 2024. Published: December 5, 2024.
1 Introduction
In order to smooth the pulse edges of the pulse-
width modulated (PWM) voltage supplied to the
terminals of induction motors (IM) from frequency
converters (FCs), output filters are used between the
FC and the IM, [1], [2], [3], [4], [5], [6], [7], [8], [9],
[10]. The negative impact of PWM voltage on
electrical equipment in the absence of an output
filter is expressed in: high-frequency noise of the IM
[11], [12], [13], increasing level of electromagnetic
interference [14], electro corrosion and destruction
of motor bearings and driven mechanisms [15],
[16], [17], [18], [19], [20], gradual degradation of
electrical insulation [21], [22], [23], accompanied
by intense generation of ozone, which is harmful to
personnel, [24], [25].
A solution to the problem is to use a sine-wave
filter (SF) (Figure 1). It brings the shape of the
output voltage of the inverter as close as possible to
a sinusoid, thereby minimizing the value of the total
harmonic distortion (THD) factor of the phase-to-
phase voltage
V
k
[26] and THD of the current
2
I
-
2I
k
[26], [27].
Fig. 1: Electrical circuit diagram of SF
(alternatively, fuses can be connected in series with
the damping resistors RA, RB and RC)
It is advisable, in any case for the frequency of
the fundamental harmonic of the output voltage of
the inverter
150f
Hz, to require that the output
voltage after the SF correspond to the grid voltage:
the THD of the supply voltage (including all
harmonics up to the order 40) shall be less than or
equal to 8 %, [26], (
V
k
no more than 12% at
WSEAS TRANSACTIONS on CIRCUITS and SYSTEMS
DOI: 10.37394/23201.2024.23.23
Mikhail Pustovetov
E-ISSN: 2224-266X
223
380 V RMS grid’s rated voltage in accordance with
Russian State Standard, [28]). The complexity of
choosing SF parameters increases at the carrier
frequency of the PWM
2
car
f
kHz - a significant
capacitance is obtained (over 1000 μF). This
circumstance forces us to pay attention to possible
features, as well as the positive and negative effects
of connecting a capacitance to the terminals of a
load containing an IM. Let's look at a few specific
provisions below.
2 Problems Formulation
1. The current through the SF capacitors increases
as the load on the IM shaft decreases.
2. In addition to the function of the SF element, the
capacitance can also perform the function of
compensating the reactive power of the IM and the
step-up transformer.
3. A significant capacitance will most likely be
composed of several parallel-connected capacitors,
possibly of different ratings and with different
characteristics.
4. The SF capacitance can form resonant circuits
with inductances in various branches of the circuit
diagram.
5. If the voltage at the inverter output fails, the SF
capacitance, remaining connected to the load circuit
containing the IM, can lead to self-excitation of the
IM, accompanied by significant currents and
voltages.
Fig. 2: An electric drive of the pump of type 14D6
(right side of the photo) as a part of WPS based on a
four-pole IM (left side of the photo) with a rated
phase-to-phase voltage of 6 kV and a rated shaft
power of
2630
rated
P
kW
Further explanations will be given using the
example of a specific technological installation - an
electric drive of the pump of type 14D6 as a part of
a water pumping station (WPS), [29], based on a
four-pole IM with a rated phase-to-phase voltage of
6 kV and a rated shaft power of
2630
rated
P
kW
(Figure 2). The calculated parameters of the IM
equivalent circuit are published in [30]. At the rated
operating mode of the pump, the load of IM is
2
0.73 rated
P
. The IM is powered using a two-
transformer circuit [9], [31] (Figure 3) from the FC
of type Vesper EI-7009-1000N (six-pulse diode
rectifier plus two-level voltage source inverter,
[32]), which has a range of PWM carrier
frequencies
1...2.5
car
f
kHz and the highest
permissible RMS output current of phase at
continuous running duty (operating mode S1), [33]
1 lim 1600I
A. The inductive branch of the SF in
each phase is represented by a pair of parallel-
connected current-limiting reactors RTST-820-
0.0505 U3 (Figure 4). The resistance of one reactor
is 1.65 mOhm. In those cases where the absence is
not specified, the presence in the diagram is implied
according to Figure 1 in the power lines of the
capacitive part of the SF damping resistors RA, RB,
and RC with a rated value of 0.013468 Ohm.
Fig. 3: The IM is powered using a two-transformer
circuit
During commissioning work with a capacitance
of the SF of 8360 μF per phase and absence in the
circuit in Figure 1 resistors RA, RB, and RC at a
frequency
1
f
of about 12 Hz, about 27 Hz and
especially 41.9-42 Hz there was a noticeable
increase in the current at the output of the inverter.
Around
142f
Hz, the inverter switched off due
to a “short circuit at the inverter output.” An
increase in current, current surges and fluctuations
in current magnitude were visible in a fairly wide
band of adjacent frequencies (bandwidth 7 Hz or
more). Therefore, using the frequency hopping IF
function will not be effective. In addition, the
current resonance frequency band may fall within
the range used for the operation and control of the
drive. By sequentially removing fuses on 1000 μF
capacitors symmetrically across the phases of the
SF, with a capacity of 3360 μF per phase, it was
possible to achieve a non-stop start of the drive with
a frequency increase rate from 0 to 50 Hz in 90 s
with the pump running on a closed gate valve, [34]
WSEAS TRANSACTIONS on CIRCUITS and SYSTEMS
DOI: 10.37394/23201.2024.23.23
Mikhail Pustovetov
E-ISSN: 2224-266X
224
(that is, with a reduced load). However, current
swings with a frequency of the order of several hertz
continued to be present, including at
150f
Hz.
When the capacity of the SF phase was reduced to
1360 μF, the fuse links burned out during the startup
of the IM without load.
Fig. 4: Pair of 3-phase current-limiting reactors
RTST-820-0.0505 U3
3 Problems Solution
The first position is illustrated in Figure 5, which
shows the calculated dependences of the SF currents
(determined by the power released at the active
resistance when current is passed through it)
according to the diagram in Figure 1 at
150f
Hz. When approximating the current graph
42
()I f P
of curve 6 in Figure 5 by the
expression y = 0.0000000001x4 - 0.0000003028x3
+ 0.0002864698x2 - 0.1487129951x +
375.429507481 the coefficient of determination,
[35], [36] is = 0.9999999995. On the contrary,
the current through the SF inductance increases with
increasing load on the IM shaft. All dependencies
shown in Figure 5, Figure 6, Figure 7, Figure 8,
Figure 9, Figure 10 and Figure 11, were obtained as
a result of computer simulation by means of
OrCAD, [37], [38], [39] of steady-state operating
modes of the electric drive.
When constructing the simulation model of an
electric drive, the following were used: approaches
and relationships for calculating SF parameters
given in [40], [41], [42], [43], [44], [45], [46], a
mathematical model of a three-phase IM, [47], [48],
[49], [50] and a three-phase transformer [51],
a computer model of autonomous voltage source
inverter, [40], [52].
Fig. 5: Calculated currents of the SF: 1 -
12
II
without capacitors at
2.5
car
f
kHz; 2 -
1
I
with
an SF capacity of 2200 μF per phase,
2.5
car
f
kHz; 3 -
1
I
at 2200 µF,
1
car
f
kHz; 4 -
1
I
at
8360 µF,
2.5
car
f
kHz and the absence of
damping resistors; 5 -
2
I
at 2200 µF,
2.5
car
f
kHz (the
2
I
curves for other cases are very close to
the one shown); 6 -
4
I
at 2200 µF,
2.5
car
f
kHz; 7 -
3
I
at 2200 µF,
2.5
car
f
kHz; 8 -
4
I
at 2200 µF,
1
car
f
kHz; 9 -
4
I
at 8360 µF,
2.5
car
f
kHz and no damping resistors
If it is necessary to determine the RMS value of
the current in a transient process, for example,
during frequency acceleration of the IM, you should
select the current curve for harmonic analysis over a
time interval equal to the period of the fundamental
harmonic. Having squared the current curve over a
period, we will then perform its harmonic analysis.
The resulting constant component will correspond to
the power that will be dissipated at the resistance of
1 Ohm when the current in question flows through
it. That is, the square root of the resulting constant
component is the RMS value of the current, taking
into account all harmonics over the selected time
interval.
The second position is also confirmed in Figure
5: with a capacitance per phase of the SF of 2200
μF, the current at the output of the SF (load current)
exceeds the current at the input of the SF (consumed
from the inverter) due to the compensation of the
reactive power of the load with the SF capacitors.
The phenomenon is known for capacitive reactive
power compensators IM, [53], [54], [55], [56], [57].
WSEAS TRANSACTIONS on CIRCUITS and SYSTEMS
DOI: 10.37394/23201.2024.23.23
Mikhail Pustovetov
E-ISSN: 2224-266X
225
From Figure 6 it can be seen that with increasing
capacity SF for
4
I
decreases
4I
k
. All other things
being equal, this occurs with an increase in
capacitance due to an increase in the proportion of
the fundamental harmonic in the harmonic spectrum
of the current
4
I
, at which reactive power
compensation occurs.
Fig. 6: Calculated specific RMS current through the
SF capacitance and the THD of the
4
I
current at
150f
Hz and load on the IM shaft equal to
2
0.05 rated
P
. The curves were obtained with
connected damping resistors. In their absence, the
specific RMS current through the capacitance is
1.3–1.4 times higher. 1 permissible specific RMS
current 0.16 A/μF for capacitors with a capacity of
1000 μF; 2 permissible specific RMS current 0.25
A/μF for capacitors with a capacity of 160 μF and
200 μF; 3 – calculated specific RMS current through
the SF capacitance; 4 -
4I
k
However, from the same Figure 5 it can be seen
that with a capacitance per SF phase of 8360 μF, the
output current of the inverter significantly exceeds
the load current and depends little on changes in the
power on the IM shaft. At the same time, the
2
I
curve is close to the case with a SF capacitance of
2200 μF. The calculation showed that to fully
compensate for the reactive power of the load when
the IM is operating in the rated mode, a SF
capacitance of 2564 μF is sufficient. That is,
“overcompensation of the reactive power of the
load by overestimating the capacity of the SF leads
to a noticeable
1
I
increase. When simulating with a
SF capacitance of 8360 μF at a low load on the IM
shaft without damping resistances for
140f
Hz
and
2.5
car
f
kHz, the specific current through
the capacitance was 0.101 A/μF, while at
145f
Hz it was already 0.181 A/μF. Accordingly, the
RMS values of the output current of the inverter at
continuous duty is 972.3 A and 1995.6 A. Thus,
around
142f
Hz there is a sharp increase of
4
I
and the output current of the inverter exceeds the
value
1 lim 1600I
A with a further increase, to
which the inverter responds by shutting down on the
basis of “short circuit at the output”. The multiple
1
I
increase in the low load mode of IM with an SF
capacitance of 8360 μF compared to the case of no
capacitance has been confirmed by tests.
The third point is illustrated by a specific
example: the SF phase capacitance of 8360 μF,
calculated from the operating condition at
1
car
f
kHz, was practically obtained by combining
capacitors with ratings of 1000 μF, 200 μF, and 160
μF. Each capacitor is protected by a fuse. The
maximum RMS values of long-term current are 40
A for 160 μF, 50 A for 200 μF and 160 A for 1000
μF. Accordingly, the long-term permissible specific
RMS current per unit of capacitance is 0.25 A/μF
for the lower ratings of capacitors, and 0.16 A/μF
for the higher ratings. Thus, if we connect as shown
in Figure 5, per phase SF 2200 μF, then based on the
sum of currents through the fuses, 370 A per phase
is permissible for a long time, and on this basis, it
should be according to Figure 5 and Figure 7, expect
that at
150f
Hz,
2.5
car
f
kHz and a load on
the IM shaft of more than
2
0.05 rated
P
, the
capacitors will not be overloaded by current in long-
term operation. But the current through parallel-
connected capacitors is distributed in direct
proportion to their capacitances. It follows that the
admissibility of loading capacitors with current in
the presence of parallel-connected high and low
ratings should be assessed by a value of 0.16 A/μF.
From Figure 7 it can be seen that only when the
power on the IM shaft is above
2
0.4 rated
P
that we
have an acceptable current load on the capacitors at
continuous duty. Otherwise, since the calculated
specific RMS capacitance current exceeds the
permissible value of 0.16 A/μF slightly, the
protection (fuse links) will be triggered, first of all,
by capacitors rated 1000 μF due to overload current
(due to overheating at continuous duty). This was
observed during the commissioning of the SF on the
WPS, when a continuous duty was tested at
WSEAS TRANSACTIONS on CIRCUITS and SYSTEMS
DOI: 10.37394/23201.2024.23.23
Mikhail Pustovetov
E-ISSN: 2224-266X
226
150f
Hz and no load condition on the IM shaft
and capacitors on the SF phase of 2200 μF and 2000
μF (fuses’ elements melting within 10 - 15 minutes)
or 1000 μF (fuses’ elements melting within 5
minutes).
Fig. 7:
4
I
and the specific RMS capacitance current
as a function of the power on the IM shaft for the
case of capacitance in the SF phase of 2200 μF,
150f
Hz and
2.5
car
f
kHz: 1 - ; 2 highest
permissible RMS current at continuous duty
4 lim 370I
A; 3 specific RMS current through
capacitance at continuous duty; 4 - highest (equal to
0.16 A/μF) permissible specific RMS current
through capacitance at continuous duty
From Figure 6 it follows that with a shaft power
of IM equal to
2
0.05 rated
P
,
150f
Hz and
2.5
car
f
kHz, we have a permissible load of
capacitors by current in a continuous duty with a
capacitance in the SF phase of at least 7160 μF, if
damping resistors are connected.
With the adopted current-limiting reactors in the
inductive part of the IF output filter, it can perform
the functions of the SF with a capacitance value per
phase of at least 360 μF at
2.5
car
f
kHz. To
create a capacitance of 360 μF, only capacitors of
160 μF and 200 μF ratings with a large permissible
specific current are used. But in this case, the value
of the calculated specific RMS current is almost
twice as high as 0.25 A/μF (Figure 6). You should
expect rapid burnout of the fuses protecting the
capacitors due to inrush current such as short circuit
current. When carrying out commissioning work on
the SF with a capacity of 360 μF per phase, the
melting of the fuses’ elements occurred already
during the frequency start-up of an unloaded IM at
120...25f
Hz (approximately 40 s after the
start of the frequency acceleration of the IM). The
fuses’ bodies didn't even have time to heat up.
Figure 8 shows the calculated graphs of the
specific RMS currents of the SF capacitances at
continuous duty as a function of the frequency of
the output voltage of the inverter for three values of
capacitance in the SF phase at low loads on the IM
shaft in case of the presence of damping resistors
RA, RB and RC in the capacitive part of the SF.
Fig. 8: Specific RMS current at continuous duty
through capacitance and
4I
k
as a function of the
frequency of the output voltage of the inverter for
cases of capacitance in the SF phase of 360 μF,
2200 μF and 8360 μF at
2.5
car
f
kHz, low loads
on the IM shaft and connected damping resistors: 1 -
22
10 / rated
PP
(ratio of power on the IM shaft to
rated); 2 - specific RMS current at 360 μF; 3 -
specific RMS current at 2200 μF; 4 - specific RMS
current at 8360 μF; 5 highest permissible specific
RMS current of capacitors with ratings of 160 μF
and 200 μF at continuous duty; 6 highest
permissible specific RMS current of capacitors rated
1000 μF at continuous duty; 7, 8, 9 -
4I
k
with a
capacity of 360 μF, 2200 μF and 8360 μF,
respectively
From Figure 6 it can be seen that with a
capacitance of 8360 μF, the specific RMS current
through capacitance is below the highest permissible
value at continuous duty in the entire range of
1
f
.
At 2200 µF the specific RMS current through
capacitance is below the highest permissible value
up to
149f
Hz, and at 360 µF - only up to the
WSEAS TRANSACTIONS on CIRCUITS and SYSTEMS
DOI: 10.37394/23201.2024.23.23
Mikhail Pustovetov
E-ISSN: 2224-266X
227
frequency of
125f
Hz. Moreover, at 360 μF,
the highest current load of the capacitors is observed
at
145f
Hz, and not at
150f
Hz, as in the
other two cases. In all cases, there is a decreasing
trend for
4I
k
with increasing frequency. But at
8360 µF
4I
k
increases slightly above 40 Hz, and at
2200 µF – above 45 Hz of fundamental frequency.
The fourth position regarding the occurrence of
resonances of the SF capacitances with the AC grid
side of the drive is impossible due to the one-way
conductivity of the diodes of the input uncontrolled
rectifier (6 pulse, bridge type) of the FC. As can be
seen from Figure 7,
C
I
, consumed from the AC
grid by the electric drive (current of the high-voltage
winding of the step-down transformer) weakly
depends on the presence and parameters of the SF. It
should be noted that there is a slight increase of
C
I
in the presence of SF compared to its absence (by 1–
41%, higher values correspond to a lower IM load).
For the current consumed from the AC grid
IC
k
also varies somewhat depending on the SF capacity
(Figure 9).
There is a possibility of resonance phenomena
occurring between the inductive elements of the FC
and the SF capacitors, as well as between the SF
capacitors and the load inductances.
In [58], in paragraph 3.4 regarding the SF it is
said: “The LC filter allows you to form a voltage
waveform close to a sinusoidal one in the motor. In
some cases, a dissipative element is added to the LC
filter - a resistor, the inclusion of which eliminates
the possibility of shock excitation processes
occurring due to cyclic energy exchange in the
“filter capacitance - motor inductance circuit. In
order to dampen possible resonant current
oscillations in circuits containing SF capacitors, it
was decided to connect resistors RA, RB, and RC in
the capacitor power lines (Figure 1). Such technical
solutions are used by electrical engineering
companies, [59], [60]. Resistances of 0.013468
Ohms were selected, allowing for long-term
dissipation of up to 8 kW per SF phase at
continuous duty. Computer simulation has shown
that it is possible to satisfy the limitation on power
dissipation in resistors, taking into account the very
complex harmonic composition of the currents
through them, only with an SF phase capacitance of
no more than 2360 μF. The temperature of the
resistances during tests without blowing was 172
°C, which indicates the need for their forced
cooling. Figure 10 shows the calculated energy
characteristics of the SF with a capacity of 2200 μF
per phase at
150f
Hz,
2.5
car
f
kHz, and
32.3
V
k
% for the linear voltage at the input of
the SF. In the case of a
car
f
decrease, all other
things being equal, the energy characteristics of the
SF deteriorate.
Fig. 9: Current consumed from the AC grid by the
electric drive at
150f
Hz: 1 -
C
I
at
2.5
car
f
kHz, SF absence or in case a capacitance of 2200 μF
per phase and damping resistors connected; 2 -
C
I
at
2.5
car
f
kHz, capacitance 8360 μF per SF
phase without damping resistors; 3 -
C
I
at
1
car
f
kHz, capacitance 2200 μF per phase SF
and damping resistors connected; 4 -
СI
k
at
2.5
car
f
kHz and SF absence; 5 -
СI
k
at
1
car
f
kHz, capacitance 2200 μF per phase and
damping resistors connected; 6 -
СI
k
at
2.5
car
f
kHz, capacitance 8360 μF per phase
without damping resistors; 7 -
СI
k
at
2.5
car
f
kHz, capacitance 2200 µF per phase and damping
resistors connected
There is a possibility of resonance phenomena
occurring between the inductive elements of the FC
and the SF capacitors, as well as between the SF
capacitors and the load inductances.
Figure 11 indicates the effectiveness of the
influence of SF on the harmonic composition of the
WSEAS TRANSACTIONS on CIRCUITS and SYSTEMS
DOI: 10.37394/23201.2024.23.23
Mikhail Pustovetov
E-ISSN: 2224-266X
228
current. The largest parasitic current
2
I
harmonic is
the 5th.
According to Figure 10 and Figure 11, we can
conclude that the SF characteristics are quite
satisfactory at
150f
Hz and
2.5
car
f
kHz,
excluding excessive specific current through the
capacitance at low IM loads (Figure 6, Figure 7 and
Figure 8). In other words, such an SF can be
operated with a motor shaft power exceeding
2
0.4 rated
P
. It is impossible to carry out
commissioning work on a drive with such an SF
without a load on the shaft or with a low load at
continuous duty. It is quite possible to operate the
SF in the entire range of IM loads at
149f
and
2.5
car
f
kHz. At
1
car
f
kHz, operation of the
SF is impossible.
Fig. 10: Calculated energy characteristics of the SF:
1 -
2I
k
; 2 SF’s total losses; 3 - THD of phase-to-
phase voltage at the load
V
k
; 4 per phase power
losses on the damping resistance; 5 voltage drop
from the fundamental harmonic in the SF phase
While allowing for reliable, trouble-free start of
the drive, the introduction of damping resistors did
not completely eliminate low-frequency current
fluctuations (on the order of several hertz) at the
inverter output at some output voltage frequencies.
During tests with a SF capacitance of 2000 μF per
phase, fluctuations in the effective current value
were up to 17% of the average value at
150f
Hz
and over 11% at
138f
Hz. An increase in
current during acceleration is noted to
approximately
130f
Hz. Above a frequency of
30 Hz, a decrease in
1
I
current values followed.
Since during the tests the rate of increase in
frequency by the converter was set to 50 Hz for 90
s, the phenomena of the inrush current of the IM
should have ended before reaching a frequency of
30 Hz.
Fig. 11: Calculated THDs for SF currents: 1 -
1I
k
;
2 -
2I
k
; 3 -
34II
kk
Therefore, it is possible that there are resonance
phenomena in the amplitudes of the FC and IM
currents. During the analysis of the results of
computer simulation, it was noted that with the
power of
2
0.05 rated
P
on the IM shaft at various
values, there are fluctuations in the rotor speed with
a frequency of approximately
5...7.25
cr
f
Hz
(arithmetic mean 6.125 Hz). Their presence in the
simulation results is not related to the size or
absence of SF capacity. Under low load conditions,
during oscillations of the rotor speed, periodic
outputs of the IM into generator mode are possible.
The amplitude of the IM phase current
2
I
and the
amplitude of the output current of the inverter
1
I
have the same oscillation period. There are also
fluctuations in the power released at the resistances
of the reactors and damping resistors, the same
frequency as the fluctuations in the rotation speed of
the IM rotor. Power fluctuations are most noticeable
at
125f
Hz and 35 Hz. Accordingly, the
oscillation frequencies are about 5 Hz and 6.67 Hz.
The same frequencies of amplitude oscillations are
recorded in the results of modeling the drive
network current. An increase in the mains current as
a result of such fluctuations could explain the
isolated cases of tripping of the step-down
transformer protection recorded during testing. The
frequency values of the inverter output voltage, for
which an increase in
1
I
amplitude was observed
WSEAS TRANSACTIONS on CIRCUITS and SYSTEMS
DOI: 10.37394/23201.2024.23.23
Mikhail Pustovetov
E-ISSN: 2224-266X
229
during testing and simulation, namely: 12 Hz, 25
Hz, 27 Hz, 35 Hz, 38 Hz, 42 Hz, 47 Hz, 50 Hz, are
close to numbers that are multiples of
cr
f
.
In [61], it is indicated that for powerful IM
powered by high-voltage FC, drives pumping unit,
the occurrence of self-oscillations of current and
rotation speed is possible. In other words,
manifestations of
1
I
current resonant phenomena
are possible. There is no mention in [61] of the
presence or absence of FC’s output filters in the
circuit. The main criterion for the propensity of the
IM to enter resonance in [61] is the value of the
magnetic flux transmission coefficient between the
stator and the rotor
0.95k
12
/k L L L L L
(1)
For IM used on the WPS, the components of (1)
have the values indicated in Table 1.
It is obvious that a particular IM meets the
criterion of propensity to enter into resonance, since
the calculated
0.955 0.95k
. It is possible
that the presence of a capacitive energy storage
device at the load terminals contributes to the
aggravation of the manifestations of this tendency
since no noticeable low-frequency
1
I
current
swings were recorded during tests when starting the
drive without an SF.
The fifth position is reflected, for example, in
[54], [62], where a correspondence is established
between the rated power of the IM at 0.4 kV line
voltage with a synchronous rotation speed of 1500
rpm and the maximum reactive power of
compensating capacitors, kVAr, connected to the
motor terminals, guaranteeing the absence of self-
excitation of IM (Table 2 in Appendix). From Table
3 (Appendix) it follows that the capacitances of
powerful SFs for operation at
2
car
f
kHz of
known manufacturers [63], [64], [65] meet the
requirements of Table 2 (Appendix). Low
capacitance in the SF is achieved by increasing the
inductance, which in some cases leads to a voltage
drop across the inductance of more than 10%.
However, [54], [62] do not deny the possibility of
using capacitances larger than those recommended.
A possible compromise solution for using SF in
a two-transformer circuit for powering a medium-
voltage IM from a low-voltage inverter is to install
medium-voltage capacitors [66] on the terminals of
the high-voltage winding of a step-up transformer,
the leakage inductance of which in this case serves
as the inductance of the SF.
Table. 1 Values of the components of (1), [58]
Main
inductance
of the IM
L
, H
Stator
winding
phase
leakage
inductance
1
L
, H
Leakage
inductance
of the rotor
squirrel cage
reduced to
the stator
phase
2
L
, H
Magnetic
flux
transfer
coefficient
between
stator and
rotor
k
,
p.u.
IM of rated shaft power 630 kW, synchronous speed
1500 rpm, rated linear RMS voltage 6 kV
0.277214
0.01084367
0.01518114
0.955
The advantages of this solution: the capacitance
of the SF is small and is formed by a single
capacitor per phase, the recommendations of Table
2 (Appendix) are satisfied (if we assume that the
maximum reactive power of capacitors that can be
connected to the IM terminals without the risk of
self-excitation does not depend on voltage). The
disadvantage will be the lack of protection through
the SF step-up transformer. For WPS, in some
cases, this option is acceptable, since the
phenomenon of ozonation needs to be eliminated in
rooms where people are. IM with pumping units
installed in the machine room where personnel
work. Transformers are installed in separate boxes
where public access is limited.
In the case under consideration with a medium-
voltage IM with a power of 630 kW, medium-
voltage capacitors KEK1-6.3-75, connected in a star
configuration, can be used (Figure 12 in Appendix).
The capacitor capacity is 6 µF. Each capacitor is
connected to the rated phase voltage
6300 / 3 3467
Cphrated
V
V. The rated
current of the capacitor is calculated from the rated
reactive power and rated voltage:
75000 11.905
6300
Crated
Сrated
Crated
Q
IV
A. The
capacitor allows a current overload of 30%. At rated
current and phase voltage, the reactive power of the
three phases of the SF capacitors will be
33 3 3467 11.905
C ph Cphrated Crated
Q V I
123823.9
VAr, that is, 123.8 kVAr, which is
slightly more than the limit value (123 kVAr) from
the Table 2 (Appendix). The nature of the
dependence of the current through the capacitor on
the load on the IM shaft is the same as with low-
voltage capacitors: at a constant voltage frequency,
as the load increases, the current through the SF
capacitors decreases. That is, the capacitor current
for no load mode will be greatest. By simulating
WSEAS TRANSACTIONS on CIRCUITS and SYSTEMS
DOI: 10.37394/23201.2024.23.23
Mikhail Pustovetov
E-ISSN: 2224-266X
230
with the IM
2
0.05 rated
P
loaded, the RMS value
of the current through the capacitor SF in a steady
state is 11.439 A, which is lower than the rated
current. RTST reactors in this case are practically
not a significant part of the SF inductance - mainly
its function is performed by the leakage inductances
of the windings of the TSZGLF 1250/10 U3
transformer, used as a step-up, for which, in a first
approximation, the sum of the leakage inductances
of the windings is
12
2 0.0036 0.0072LL
H.
Then
/ 2500 / 765.7 3.265
car r
ff
.
4 Conclusions
1. When using SF capacitances composed of
parallel-connected capacitors with different
characteristics, the smallest possible value of the
specific RMS current through the capacitor should
be taken as a current limit.
2. When using SF capacitors made up of a specific
set of parallel-connected capacitors with different
ratings, it should be possible for the consumer to use
different combinations of capacitor ratings, allowing
the SF capacitor to be adjusted for specific operating
conditions. It should be possible to operate the SF
both without and with damping resistors in the
capacitive part.
3. SF capacitors are most loaded with current in case
of the no-load mode of IM (or another load device).
The SF must provide the ability to operate at
continuous duty with real no-load mode, for
example, IM, over the entire range of output voltage
and frequency of the inverter. This is very important
for commissioning work.
4. In the SF, you should not use a capacitance larger
than that suitable to ensure full compensation of the
reactive power of the load. Violation of this rule
leads to an unjustified increase in the output current
of the inverter and the current through the SF
capacitors.
5. The method for calculating the RMS value of the
current through the capacitance of the SF should
ensure correct consideration of the contribution of a
wide range of higher temporal harmonics. It is
advisable to carry out a computer simulation of
the steady-state operating modes of the drive to
calculate the RMS value of the current through the
capacitance, and dynamic modes to identify the
maximum instantaneous current values. Calculation
of the RMS value of the current through the SF
capacitance using the method described in [67] (for
example: Trace expression-> SQRT(S(I(R5)*
I(R5))/Time), based on the results of the dynamic
modes of the drive simulation, can lead to
underestimated values if the long-range steady-state
cycle has not been reached.
6. Reducing the specific RMS current through the
SF capacitance by increasing the resistance of
damping resistors is impractical. For example, a
twofold increase in resistance leads to an increase in
losses on it by 83% while the specific RMS current
through the SF capacitance decreases by only 4%.
7. As a rule, capacitors of type “AC filtering” are
suitable for composing the SF capacitance. The
main characteristics for selection will be the voltage
amplitude on the capacitor and the amplitude of the
current through the capacitor. It is also necessary to
take into account the RMS voltage across the
capacitor and the RMS current through the
capacitor. In order to prevent an overcurrent when
choosing a capacitor, it is recommended that, having
calculation or simulation result on the amplitude of
the current through the capacitor, calculate the RMS
value of the current from its amplitude as for a
sinusoidal waveform, i.e. dividing the calculated
amplitude value of the current through the capacitor
by
2
. The RMS value of the current through the
capacitor obtained as a result of the calculation
should be further used to select a capacitor from the
catalog [68], [69], [70] if it also indicates the RMS
value under the name Imax, acting on the principle
“select a value from the catalog that is not less than
the calculated one”. Maximum current
max
I
the
maximum permissible RMS value of the current
through the capacitor in continuous operation, this
value is usually given in the technical specifications,
it determines the maximum power dissipated by the
capacitor. Also, when choosing a capacitor, you can
focus on the peak repeating current
ˆ
I
- this is the
permissible current amplitude in a repeating mode.
The current
ˆ
I
exceeds
max
I
from 3 to 40 and more
times. For the selected capacitors, you should select
a suitable protection device against overcurrents and
overload currents.
References:
[1] M.Y. Pustovetov, Voinash S.A., "Analysis of
dv/dt Filter Parameters Influence on its
Characteristics. Filter Simulation Features,"
2019 International Conference on Industrial
Engineering, Applications and Manufacturing
(ICIEAM), Sochi, Russia, 2019, pp. 1-5,
https://doi.org/10.1109/ICIEAM.2019.874300
7.
WSEAS TRANSACTIONS on CIRCUITS and SYSTEMS
DOI: 10.37394/23201.2024.23.23
Mikhail Pustovetov
E-ISSN: 2224-266X
231
[2] Pastura M., Nuzzo S., Kohler M., Barater D.,
"Dv/Dt Filtering Techniques for Electric
Drives: Review and Challenges," IECON
2019 - 45th Annual Conference of the IEEE
Industrial Electronics Society, Lisbon,
Portugal, 2019, pp. 7088-7093, https://doi.org/
10.1109/IECON.2019.8926663.
[3] Haider M., Niklaus P.S., Madlener M.,
Rohner G., Kolar J.W., Comparative
Evaluation of Gate Driver and LC-Filter
Based dv/dt-Limitation for SiC-Based Motor-
Integrated Variable Speed Drive Inverters,
IEEE Open Journal of Power Electronics,
Vol. 4, 2023, pp. 450-462.
https://doi.org/10.1109/OJPEL.2023.3283052.
[4] Pontt J., Rodriguez J., Kouro S., Silva C.,
Farias H., Rotella M., "Output sinus filter for
medium voltage drive with direct torque
control," Fourtieth IAS Annual Meeting.
Conference Record of the 2005 Industry
Applications Conference, Hong Kong, China,
2005, pp. 204-209 Vol. 1,
https://doi.org/10.1109/IAS.2005.1518311.
[5] Arhin B., Cha H., "A New dv/dt Filter Design
Method using the Voltage Reflection Theory,"
2022 4th Global Power, Energy and
Communication Conference (GPECOM),
Nevsehir, Turkey, 2022, pp. 107-111,
https://doi.org/10.1109/GPECOM55404.2022.
9815657.
[6] Anirudh Acharya B., John V., "Design of
output dv/dt filter for motor drives," 2010 5th
International Conference on Industrial and
Information Systems, Mangalore, India, 2010,
pp. 562-567,
https://doi.org/10.1109/ICIINFS.2010.5578641
[7] Mart-ro P., Sae-Kok W., Khomfoi S.,
"Analysis of dv/dt filter installation for PWM
AC drive applications," 2011 IEEE Ninth
International Conference on Power
Electronics and Drive Systems, Singapore,
2011, pp. 177-184,
https://doi.org/10.1109/PEDS.2011.6147243.
[8] Baek S., Choi D., Bu H., Cho Y., Analysis and
Design of a Sine Wave Filter for GaN-Based
Low-Voltage Variable Frequency Drives,
Electronics, Vol. 9, No. 345, 2020, pp. 1-12.
https://doi.org/10.3390/electronics9020345.
[9] Dresvianskii E., Pokushko M., Stupina A.,
Panteleev V., Yurdanova V., Control of high-
voltage pump motor using a frequency sine-
wave filter converter, IOP Conference Series:
Materials Science and Engineering, Vol. 450,
Iss. 7, No. 072003, 2018, pp. 1-6.
https://doi.org/10.1088/1757-
899X/450/7/072003.
[10] Petrov V.L., Pichuev A.V., Assessing the
efficiency of measures to enhance electric
power quality in variable-frequency drive for
scraper conveyors, Mining Science and
Technology (Gornye nauki i tekhnologii), Vol.
9 (1), 2024, pp. 60-69.
https://doi.org/10.17073/2500-0632-2024-01-
198.
[11] Marignetti F., Rubino G., Boukadida Y.,
Conti P., De Gregorio F., Iengo E.,
Longobardi V.G., "Noise and vibration
analysis of an inverter-fed three-phase
induction motor," 2020 International
Symposium on Power Electronics, Electrical
Drives, Automation and Motion (SPEEDAM),
Sorrento, Italy, 2020, pp. 157-161,
https://doi.org/10.1109/SPEEDAM48782.202
0.9161859.
[12] Belmans R.J.M., Noise in Inverter-Fed
Squirrel-Cage Induction Motors. In: Ertan,
H.B., Üçtuğ, M.Y., Colyer, R., Consoli, A.
(eds) Modern Electrical Drives. NATO ASI
Series, Vol. 369. Springer, Dordrecht, 2000.
https://doi.org/10.1007/978-94-015-9387-
8_26.
[13] Delgado-Arredondo P.A., Romero-Troncoso
R.J., Duque-Pérez O., Morinigo-Sotelo D.,
Osornio-Rios R.A., "Vibration, Acoustic
Noise Generation and Power Quality in
Inverter-fed Induction Motors," 2019 IEEE
12th International Symposium on Diagnostics
for Electrical Machines, Power Electronics
and Drives (SDEMPED), Toulouse, France,
2019, pp. 412-418,
https://doi.org/10.1109/DEMPED.2019.88648
44.
[14] Hughes A., Drury B., Chapter Eight -
Inverter-fed Induction Motor Drives, Editors:
Austin Hughes, Bill Drury, Electric Motors
and Drives (Fourth Edition), Newnes, 2013,
pp. 255-279, https://doi.org/10.1016/B978-0-
08-098332-5.00008-5.
[15] Tsikhalevsky I., Vakhrushev K., Rusakov A.,
"Analysis of the causes of failures of TED
bearings of Lastochka electric trains," AIP
Conf. Proc., Vol. 2624, No. 020032, 2023.
https://doi.org/10.1063/5.0132813.
[16] Ma J., Xue Y., Han Q., Li X., Yu C.. Motor
Bearing Damage Induced by Bearing Current:
A Review, Machines, Vol. 10 (12), No. 1167,
2022, pp. 1-23.
https://doi.org/10.3390/machines10121167.
WSEAS TRANSACTIONS on CIRCUITS and SYSTEMS
DOI: 10.37394/23201.2024.23.23
Mikhail Pustovetov
E-ISSN: 2224-266X
232
[17] Sundaresan A., Chandorkar M., "Traction
Motor Bearing Failures Due to Bearing
Currents in Electric Locomotives," 2019 IEEE
Transportation Electrification Conference
and Expo (ITEC), Detroit, MI, USA, 2019,
pp. 1-6,
https://doi.org/10.1109/ITEC.2019.8790569.
[18] Vostrov K., Pyrhönen J., Ahola J., "Shielding
the end windings to reduce bearing currents,"
2020 International Conference on Electrical
Machines (ICEM), Gothenburg, Sweden,
2020, pp. 1431-1437,
https://doi.org/10.1109/ICEM49940.2020.927
0673.
[19] Zelentsov V., Ippolitov V., Dyshlevoy I., "A
technique analysis of ways to compensate
high-frequency currents on traction electric
machines mechanical units," 2021 XVIII
International Scientific Technical Conference
Alternating Current Electric Drives (ACED),
Ekaterinburg, Russia, 2021, pp. 1-4,
https://doi.org/10.1109/ACED50605.2021.946
2315.
[20] Zheng J., Xiang D., Li H., Quach D.-C., "An
Investigation into the Effect of Bearing
Grease Degradation on the High-frequency
dv/dt Bearing Current in an Inverter-fed
Motor System," 2021 6th International
Conference on Power and Renewable Energy
(ICPRE), Shanghai, China, 2021, pp. 543-
547,
https://doi.org/10.1109/ICPRE52634.2021.96
35227.
[21] Alvarez-Gonzalez F., Hewitt D., Griffo A.,
Wang J., Diab M., Yuan X., "Design of
Experiments for Stator Windings Insulation
Degradation under High dv/dt and High
Switching Frequency," 2020 IEEE Energy
Conversion Congress and Exposition (ECCE),
Detroit, MI, USA, 2020, pp. 789-795,
https://doi.org/10.1109/ECCE44975.2020.923
5940.
[22] Petrarca C., Egiziano L., Tucci V., Vitelli M.,
"Investigation on performances of insulation
materials for inverter-fed traction motors,"
1998 Annual Report Conference on Electrical
Insulation and Dielectric Phenomena (Cat.
No.98CH36257), Vol. 2, Atlanta, GA, USA,
1998, pp. 564-567,
https://doi.org/10.1109/CEIDP.1998.732960.
[23] Saeed M., Fernández D., Guerrero J.M., Díaz
I., Briz F., Insulation Condition Assessment in
Inverter-Fed Motors Using the High-
Frequency Common Mode Current: A Case
Study. Energies, Vol. 17 (2), No. 470, 2024,
pp. 1-16, https://doi.org/10.3390/en17020470.
[24] Ozone: Health hazards and control measures.
Guidance Note EH38, [Online].
https://www.hse.gov.uk/pubns/eh38.pdf
(Accessed Date: June 23, 2024).
[25] Dmitriev V., Oliveira R.M.S., Zampolo R.F.,
Moutinho de Vilhena P.R., de Souza Brasil F.,
Fernandes M.F., Partial Discharges and
Ozone. In: Partial Discharges in
Hydroelectric Generators. Power Systems.
Springer, Cham., 2024.
https://doi.org/10.1007/978-3-031-36604-8_7.
[26] European Standard UNE EN 50160:2023.
Voltage characteristics of electricity supplied
by public electricity networks, [Online].
https://cdn.standards.iteh.ai/samples/71003/49
0b981fbec343edb9db83f8ce4b2b3d/SIST-
EN-50160-2023.pdf (Accessed Date: October
21, 2024).
[27] Holmes D.G., Lipo T.A., Pulse width
modulation for power converters: principles
and practice, Hoboken, NJ: John Wiley, 2003,
[Online].
https://ieeexplore.ieee.org/book/5264450
(Accessed Date: October 21, 2024).
[28] State Standard GOST R 54149-2010. Electric
energy. Electromagnetic compatibility of
technical equipment. Standards for the quality
of electrical energy in general-purpose power
supply systems, Moscow, Russia:
Standartinform, 2012, [Online].
https://files.stroyinf.ru/Data/524/52435.pdf?ys
clid=m2iwtsqvmu547869952 (Accessed Date:
October 21, 2024).
[29] Jones G.M., Bosserman II B.E., Sanks R.L.,
Tchobanoglous G., Pumping Station Design,
3d edition, Butterworth-Heinemann, 2006,
[Online].
https://vdoc.pub/download/pumping-station-
design-third-edition-od4s9sn73ps0 (Accessed
Date: October 11, 2024).
[30] Pustovetov M., Shukhmin K., Goolak S.,
Matijošius J., Kravchenko K., Induction
Motor Computer Models in Three-Phase
Stator Reference Frames: A Technical
Handbook, Bentham Science Publishers Pte.
Ltd. Singapore, 2023.
https://doi.org/10.2174/97898151243091230101
[31] H. Mahdi, B. Hoff, T. Østrem, A Review of
Power Converters for Ships Electrification,
IEEE Transactions on Power Electronics,
Vol. 38, No. 4, pp. 4680-4697, 2023,
https://doi.org/10.1109/TPEL.2022.3227398.
WSEAS TRANSACTIONS on CIRCUITS and SYSTEMS
DOI: 10.37394/23201.2024.23.23
Mikhail Pustovetov
E-ISSN: 2224-266X
233
[32] Bin Wu, Mehdi Narimani, High-Power
Converters and AC Drives, 2nd edition,
Wiley-IEEE Press, 2017.
https://doi.org/10.1002/9781119156079.
[33] Standard IEC 60034-1:2022. Rotating
electrical machines - Part 1: Rating and
performance, [Online].
https://webstore.iec.ch/en/publication/65446
(Accessed Date: October 11, 2024).
[34] Parisher R.A., Rhea R. A.. Pipe Drafting and
Design. Fourth Edition, Gulf Professional
Publishing, 2021.
https://doi.org/10.1016/C2019-0-01022-9.
[35] Chicco D., Warrens M.J., Jurman G., The
coefficient of determination R-squared is
more informative than SMAPE, MAE,
MAPE, MSE and RMSE in regression
analysis evaluation, PeerJ Computer Science,
Vol. 7, No. e623, 2021.
https://doi.org/10.7717/peerj-cs.623.
[36] Kvalseth T.O., Cautionary Note about R2, The
American Statistician, Vol. 39, No. 4, Part 1,
Nov., 1985, pp. 279-285.
https://doi.org/10.2307/2683704.
[37] Keown J, OrCAD PSpice and Circuit
Analysis, 4th edition, Prentice Hall, 2000.
[38] Rashid M.H., SPICE for Power Electronics
and Electric Power, 3rd edition, Boca Raton,
USA: CRC Press, 2012.
https://doi.org/10.1201/b12105.
[39] Fitzpatrick D., Analog Design and Simulation
Using OrCAD Capture and PSpice, 2nd
edition, Newnes, 2017.
[40] Pustovetov M., Determining the Parameters of
the Sine-Wave Filter. Factors Affecting
Filtration Quality. Journal of Engineering
Research and Sciences, Vol.1, No.4, 2022,
pp.127-136.
https://doi.org/10.55708/js0104015.
[41] Niu Yanshu, “Single Phase Sine Wave PWM
Inverter Circuit Simulation and the Design of
Filter Based on Matlab,” 2018 2nd
International Conference on Electronic
Information Technology and Computer
Engineering (EITCE 2018), MATEC Web
Conf., Vol. 232, No. 04030, 2018, pp. 1-4,
https://doi.org/10.1051/matecconf/201823204
030.
[42] Nerubatskyi V., Plakhtii O., Hordiienko D.,
Mykhalkiv S., Ravluyk V., A Method for
Calculating the Parameters of the Sine Filter
of the Frequency Converter, Taking into
Account the Criterion of Starting Current
Limitation and Pulse-Width Modulation
Frequency, Eastern-European Journal of
Enterprise Technologies (EEJET), No. 1 (8
(109)), 2021, pp. 6-16,
https://doi.org/10.15587/1729-
4061.2021.225327.
[43] Ansari M.I., Misra H., "Impact of Sine-Wave
LC filter on Two-Level PWM VSI fed IM
drive considering the long leads," 2020 21st
National Power Systems Conference (NPSC),
Gandhinagar, India, 2020, pp. 1-6,
https://doi.org/10.1109/NPSC49263.2020.933
1949.
[44] Vdovin V.V., Kotin D.A., Pankratov V.V.,
"Parameters determination in the sine filters
for AFE converters and VSI with PWM,"
2014 15th International Conference of Young
Specialists on Micro/Nanotechnologies and
Electron Devices (EDM), Novosibirsk,
Russia, 2014, pp. 383-386,
https://doi.org/10.1109/EDM.2014.6882553.
[45] Zehelein M., Fischer M., Nitzsche M., Roth-
Stielow J., "Influence of the Filter Design on
Wide-Bandgap Voltage Source Inverters with
Sine Wave Filter for Electrical Drives," 2019
21st European Conference on Power
Electronics and Applications (EPE '19 ECCE
Europe), Genova, Italy, 2019, pp. 1-10,
https://doi.org/10.23919/EPE.2019.8914968.
[46] Cacciato M., Scarcella G., Scelba G.,
Pecoraro G., "Genetic algorithms based
design technique of sine wave filters for AC
motor drives," 2014 ELEKTRO, Rajecke
Teplice, Slovakia, 2014, pp. 208-213,
https://doi.org/10.1109/ELEKTRO.2014.6847
902.
[47] Pustovetov M.Y., "A mathematical model of
the three-phase induction motor in three-phase
stator reference frame describing
electromagnetic and electromechanical
processes," 2016 Dynamics of Systems,
Mechanisms and Machines (Dynamics),
Omsk, Russia, 2016, pp. 1-5,
https://doi.org/10.1109/Dynamics.2016.78190
69.
[48] Goolak S., Liubarskyi B., Sapronova S.,
Tkachenko V., Riabov Ie. “Refined model of
asynchronous traction electric motor of
electric locomotive,” The proceedings of the
25th International Scientific Conference
Transport Means 2021 - Sustainability:
Research and Solutions, Part I, Kaunas,
Lithuania, 2021, pp. 455-460, [Online].
https://transportmeans.ktu.edu/wp-
content/uploads/sites/307/2018/02/Transport-
Means-2021-Part-I.pdf (Accessed Date: June
23, 2024).
WSEAS TRANSACTIONS on CIRCUITS and SYSTEMS
DOI: 10.37394/23201.2024.23.23
Mikhail Pustovetov
E-ISSN: 2224-266X
234
[49] Goolak S., Gorobchenko O., Nezlina O.,
Riabov I., Yurchenko V., Improvement of the
model of an asynchronous traction motor of
an electric locomotive by taking into account
power losses, Przeglad Elektrotechniczny,
Vol. 98, No. 5, 2022, pp. 1-10.
https://doi.org/10.15199/48.2022.05.01.
[50] Goolak S., Liubarskyi B., Sapronova S.,
Tkachenko V., Riabov I., Glebova M.,
Improving a model of the induction traction
motor operation involving non-symmetric
stator windings, Eastern-European Journal of
Enterprise Technologies, Vol. 4, No. 8-112,
2021, pp. 45-58.
https://doi.org/10.15587/1729-
4061.2021.236825.
[51] Pustovetov M.Y., A universal mathematical
model of a three-phase transformer with a
single magnetic core, Russian Electrical
Engineering, Vol. 86, 2015, pp. 98–101.
https://doi.org/10.3103/S106837121502011X.
[52] Kabalyk I., Gutsol A., “Simulation of control
and measurement systems for dc-ac inverter,”
International Scientific Conference Topical
Problems of Architecture, Civil Engineering
and Environmental Economics (TPACEE-
2018), E3S Web of Conferences., Vol. 91,
No. 01008, 2019, pp. 1-8.
https://doi.org/10.1051/e3sconf/20199101008.
[53] Juromskiy V.M., Engineering model of the
electric drives of separation device for
simulation of automatic control systems of
reactive power compensation by means of
serially connected capacitors, Journal of
Physics: Conference Series, Vol. 751, No.
012010, 2016. https://doi.org/ 10.1088/1742-
6596/751/1/012010.
[54] Electrical installation guide. According to IEC
international standards. Schneider Electric,
[Online]. https://download.schneider-
electric.com/files?p_enDocType=Technical+l
eaflet&p_File_Name=Electrical+Installation+
Guide+2018.pdf&p_Doc_Ref=EIGED306001
EN (Accessed Date: June 23, 2024).
[55] Fazal M, Waleed Raza M, Khan S, Faizullah,
Reactive Power Compensation by Power
Capacitor Method, Engineering Technology
Open Access Journal, Vol. 1 (3), No. 555565,
2018, pp. 0092-0095.
https://doi.org/10.19080/ETOAJ.2018.01.555
565.
[56] Kazakbaev V., Oshurbekov S., Prakht V.,
Dmitrievskii V., Feasibility Study of Direct-
on-Line Energy-Efficient Motors in a
Pumping Unit, Considering Reactive Power
Compensation, Mathematics, Vol. 9, No.
2196, 2021, pp. 2-14.
http://doi.org/10.3390/math9182196.
[57] EATON. December 2015. Sheet 35001.
Power Factor Capacitors and Detuned Filters,
[Online].
https://www.eaton.com/content/dam/eaton/pro
ducts/design-guides---consultant-
audience/canada/cag/eaton-power-factor-
capacitors-detuned-filters-consulting-
application-guide-tb02608001e-tab-35-
ca08104001e-ca.pdf (Accessed Date: June 23,
2024).
[58] Khachaturyan V.A., Control of power supply
of oil refineries in conditions of mass use of
adjustable electric drives, St. Petersburg,
Russia: Publishing house of Peter the Great
St.Petersburg Polytechnic University, 2001.
[59] Cacciato M., Scarcella G., Scelba G., Spanik
P., Sine Wave Filters Design for AC Motor
Drives with Genetic Algorithms,
Communications - Scientific Letters of the
University of Zilina, Vol. 17(1A), 2015, pp.
102-109.
https://doi.org/10.26552/com.C.2015.1A.102-
109.
[60] MotorGuard KMG High Performance Output
Sine Wave Filter. Installation, Operation, and
Maintenance Manual. TCI, [Online].
https://files.valinonline.com/userfiles/docume
nts/tci-kmg-user-manual.pdf (Accessed Date:
June 23, 2024).
[61] Chepkunov R.A., Study of electromechanical
self-oscillations in an induction motor based
electric drive at low frequencies, Bulletin of
Kremenchug National University named after
Mikhail Ostrogradsky, No. 4/2008 (51), Part
2, 2008, pp. 17-20.
[62] EMC Filters, [Online].
https://file.elecfans.com/web1/M00/20/D5/oY
YBAFmk2Q-ACM1GAIIw7rko1CM261.pdf
(Accessed Date: June 23, 2024).
[63] Danfoss. Output Filters Design Guide,
[Online].
https://www.rpmecatronica.com/system/storag
e/download/130B2447.pdf?key=GG48eKtcD
68412CiJv4wXIE4dD8zpzLZ (Accessed
Date: June 23, 2024).
[64] Data Sheet. Sine Wave Filters FN5040HV.
Schaffner, [Online].
https://www.schaffner.com/product/FN5040H
V/Schaffner_datasheet_FN5040HV.pdf
(Accessed Date: June 23, 2024).
[65] Data Sheet. Sine Wave Filters FN5420.
Schaffner, [Online].
WSEAS TRANSACTIONS on CIRCUITS and SYSTEMS
DOI: 10.37394/23201.2024.23.23
Mikhail Pustovetov
E-ISSN: 2224-266X
235
https://www.schaffner.com/product/FN5420/S
chaffner_datasheet_FN5420.pdf (Accessed
Date: June 23, 2024).
[66] Reactive Power Compensation of High
Voltage Power System, [Online].
https://tdneoteh.ru/files/20161215-
104221_516792895.pdf (Accessed Date: June
23, 2024).
[67] Bolotovskii Yu.I., Tanazly G.I., OrCAD.
Modelirovanie “Povarennaya kniga”
(OrCAD. “Cookbook” for Simulation),
Moscow, Russia: Solon-press, 2005.
[68] Power Electronics Capacitors, [Online].
https://www.nucon.ru/upload/iblock/b42/DC-
2016.pdf (Accessed Date: June 23, 2024).
[69] Electronic Power Capacitors. EPC Series.
RTR Energia, [Online].
https://rtrenergia.es/wp-
content/uploads/2023/03/AC-FILTERING-
.pdf (Accessed Date: June 23, 2024).
[70] AC Filter Capacitors, [Online].
https://www.zez-
silko.com/data/uploadHTML/files/download-
pe-power-electronics/ac-filter-capacitors.pdf
(Accessed Date: June 23, 2024).
Contribution of Individual Authors to the
Creation of a Scientific Article (Ghostwriting
Policy)
The author equally contributed to the present
research, at all stages from the formulation of the
problem to the final findings and solution.
Sources of Funding for Research Presented in a
Scientific Article or Scientific Article Itself
No funding was received for conducting this study.
Conflict of Interest
The author has no conflicts of interest to declare that
are relevant to the content of this article.
Creative Commons Attribution License 4.0
(Attribution 4.0 International, CC BY 4.0)
This article is published under the terms of the
Creative Commons Attribution License 4.0
https://creativecommons.org/licenses/by/4.0/deed.en
_US
WSEAS TRANSACTIONS on CIRCUITS and SYSTEMS
DOI: 10.37394/23201.2024.23.23
Mikhail Pustovetov
E-ISSN: 2224-266X
236
APPENDIX
Table 2. Recommended correspondence between the rated power of the IM and the maximum reactive power
of the capacitors
Rated power of the IM,
kW
Maximum reactive power of
capacitors, kVAr
C, µF (per phase) when connected according
to a delta circuit for a RMS voltage of 0.4
kV
22
8
53
30
10
66
37
11
73
45
13
86
55
17
113
75
22
146
90
25
166
110
29
192
132
36
239
160
41
272
200
47
312
250
57
378
280
63
418
355
76
504
400
82
544
450
93
617
Subsequent values are obtained by extrapolation
500
102
675
630
123
816
800
150
994
Table. 3. Characteristics of powerful SF in accordance with [63], [64], [65] for an RMS linear voltage of 0.4 kV
Rated power of the IM, kW
C, µF (per phase) when
connected according to a delta
circuit
L, mH
Resonant frequency of SF fr,
Hz
Carrier frequency of PWM
inverter fcar, Hz
car
r
f
f
Voltage drop at a frequency of
50 Hz across the SF inductance
in % of 380 V
Inverter output current, A
250
94
0.11
903.6
3000
3.3
4.4
480
400
165
0.2
505.8
2000
4.0
12.4
750
450
188
0.11
639.0
2000
3.1
8.0
880
500
188
0.11
639.0
2000
3.1
8.0
880
560
282
0.075
631.8
2000
3.2
7.4
1200
630
282
0.075
631.8
2000
3.2
7.4
1200
800
330
0.1
505.8
2000
4.0
12.4
1500
WSEAS TRANSACTIONS on CIRCUITS and SYSTEMS
DOI: 10.37394/23201.2024.23.23
Mikhail Pustovetov
E-ISSN: 2224-266X
237
Fig. 12: Dry step-up power transformer 0.4/6 kV TSZ-1250/6/0.4 Y/Δ in an individual box. At the bottom right
you can see medium-voltage cosine capacitors KEK1-6.3-75 to 6.3 kV, 75 kVAr, connected according to the Y
circuit, acting as capacitive elements of the SF
WSEAS TRANSACTIONS on CIRCUITS and SYSTEMS
DOI: 10.37394/23201.2024.23.23
Mikhail Pustovetov
E-ISSN: 2224-266X
238