Inverter Coupled Energy Storage System for Soft-Restarting of Power
System Dynamic Load
VIKRAMSINGH R. PARIHAR1, ROHAN V. THAKUR2, DR. MOHAN B. TASARE3, HARSHADA M.
RAGHUWANSHI4, MOHINI G. FUSE5, DR. SONI A. CHATURVEDI6
1, 2, 3 Department of Electrical Engineering, Prof Ram Meghe College of Engineering and Management,
Badnera-Amravati, INDIA
4 Department of Computer Engineering, Trinity College of Engineering and Research, Pune, INDIA
5Department of Electrical Engineering, Ballarpur Institute of Technology, Ballarpur, Chandrapur, INDIA
6Department of Electronics & Communication Engineering, Priyadarshini College of Engineering, Nagpur,
INDIA
Abstract: - This paper presents the design and implementation of an inverter-coupled energy storage system (ESS)
for the soft-restarting of dynamic loads in power systems, utilizing MATLAB Simulink as the simulation platform.
The proposed system aims to enhance the reliability and stability of power grids by providing a controlled and
efficient method for restarting loads after an interruption. The inverter-coupled ESS integrates a battery storage unit
with a power inverter to supply the necessary energy for a smooth load restart, minimizing the impact on the overall
system. Simulation results demonstrate the effectiveness of the system in maintaining voltage stability, reducing
inrush currents, and ensuring a seamless transition during the load restarting process. The study highlights the
potential of inverter-coupled ESS in modern power systems, offering a robust solution for managing dynamic load
behavior and improving grid resilience.
Key-Words: - Inverter-Coupled Energy Storage System, Soft-Restarting, Power System Stability, Dynamic Load,
MATLAB Simulink, Voltage Stability, Inrush Currents, Battery Storage, Grid Resilience, Power Inverter, Load
Management, Power Grid Reliability
Received: March 28, 2023. Revised: October 15, 2024. Accepted: November 11, 2024. Published: December 9, 2024.
1. Introduction
Industrial processes like producing goods or manufacturing
any product can suffer major loss in financial means due to the
interruption of power cut. These processes get encountered
and get completed with the help of motors which are of ratings
from 0.5 to 500 hp in which 30%-35% are line connected. In
2012, Federation of Indian Chambers of Commerce & Industry
(FICCI) revealed that firms generally do not suffer any
shortfall in production due to the erratic power supply. This is
because the firms have adapted themselves to the current
power scenario so well that all that they suffer is cost
escalation due to the use of power backups to support their
production activity. However, it was considered important to
ask the industrial groups about any shortfall that they might
incur due to the intermittent power supply, in case they do not
use power backups to support their operations, the regarding
results are shown in figure 1 [1]. The main objective of the
study is to understand the impact of power outages on the
Indian industry. An analysis of the shortfall or impact on
production due to power cuts is thus paramount. Generally in
Indian industries, there are several firms which are being
converted to independent power suppliers since they require
continuous power supply to get desired output within
stipulated time to fulfil the customer’s requirement. But it is
not so reliable to consider due to occurrence of certain
mishaps which would not be predictable
International Journal on Applied Physics and Engineering
DOI: 10.37394/232030.2024.3.8
Vikramsingh R. Parihar, Rohan V. Thakur,
Dr. Mohan B. Tasare, Harshada M. Raghuwanshi,
Mohini G. Fuse, Dr. Soni A. Chaturvedi
E-ISSN: 2945-0489
52
Volume 3, 2024
Figure 1. Distribution of shortfall in production due to outages
by type of enterprises
The graph mentioned in figure 1 shows that due to power
outages, there is significant increase in the shortfall of
production of industrial grades which get noticed over not
using alternate power supply [2]. Also system transients are
also responsible for the highest number of failures of
electronic components [3].
The energy-storage systems (ESSs) can be alternative as an
auxiliary source for industrial plant is reported in studies [4]-
[6]. Some heavy industries such as Pulp and Paper (80-300
MW) commonly generate a fraction (20%) of their own energy
onsite [7]. In this paper, we use ramping power which is
supplied from a local energy-storage system (ESS) inverter.
This power is fed to the industrial power system bus and then
ensures a transient-free load transfer to the grid source. This
method is termed as ‘Soft-Restarting’ which is initiated after
an occurrence of three-phase-to-ground fault which is external
to the load zone supplied by ESS. There are certain benefits of
soft-restarting (SR) method which are as follows:
1. Automatic and continuous process.
2. No process downtime so no any external handling (labour
operation) requires to restore the system hence labour cost get
reduced.
3. Method ensures predefined inrush currents.
4. Line equipment like distribution transformer can be
downsized or their maintenance can be delayed.
5. Unsuccessful reclosing attempts get avoided after the
occurrence of faults or momentary interruptions.
6. Synchronization is achieved by the inverter to perform a
transient-free load transfer to the grid source.
2. Proposed System
In this section, the generalized view of the system and circuit
breakers operating sequence is discussed for better
understanding of the system.
2.1 Generalized View of the System
The system which is proposed in this paper is as shown in
figure 2, which includes an industrial load connected to the
industrial bus i.e. load-bus as named in the figure 1. As stated
earlier, industrial loads varies from o.5 hp to 500 hp motors, so
here the use of an asynchronous motor of rated power 400 hp
has been done which is considered as an industrial load. To
drive the load bus, bus is getting supply from grid source and
at fault condition bus gets disconnected due to the operation of
circuit breakers: circuit breaker 1 (CB_1), circuit breaker 2
(CB_2) and main circuit breaker (CB_main). The sequence of
operation of circuit breakers plays vital role in maintaining
proper condition of the network [8]. Mainly we are dealt with
the circuit breaker and relay operation to carry out the
effectiveness of the soft-restarting method. Simpler way to
carry out this process is to understand the circuit breakers
operation thoroughly and to use it in simulation. Which is
described preceding to this as below.
Figure 2. A small representative of an industrial power
network with line connected asynchronous motor
2.2 Circuit Breaker’s Operating Sequence
In this system, we are considering a fault occurrence which is a
three-phase-to-ground fault in somewhere between circuit
breaker-1 and circuit breaker-2. This fault is considered as
much severe as compared to other types of fault. Such fault
can harm or damage a system permanently [9]. Several circuit
breakers are used for the purpose of protection of system or
any equipment depending on their requirement and parameters
[10]. Following operations takes place during s oft-restarting
process.
International Journal on Applied Physics and Engineering
DOI: 10.37394/232030.2024.3.8
Vikramsingh R. Parihar, Rohan V. Thakur,
Dr. Mohan B. Tasare, Harshada M. Raghuwanshi,
Mohini G. Fuse, Dr. Soni A. Chaturvedi
E-ISSN: 2945-0489
53
Volume 3, 2024
1. A three-phase-to-ground fault takes place in between
CB_1 and CB_2.
2. Following this fault, CB_1-CB_2 and CB_main get
tripped in response to overcurrent and undervoltage relay
respectively.
3. While the system gets isolated from the load bus, then
inverter-coupled ESS starts supplying the power by closing its
circuit breaker which is normally open. ESS then supply the
ramp power to the load bus until the voltage and frequency
ratio (V/Hz) get matched to the grid source supply. This
situation is called as ramp-up process in which inverter supply
ramping power to the load bus.
4. As soon as voltage and frequency get matched, inverter
stops supplying the power and load get transferred to the grid
source by reclosing the CB_main and tripping off circuit
breaker of energy storage system (CB_ESS).
There are certain conventional practices which are used for the
reclosing of the motors after fault conditions. These
conventional practices are harmful since there is certain
amount of residual voltage present in the motors which would
be dangerous for system restoration [11]-[12]. To avoid a
possible cascaded voltage collapse that may result from this
effect, the system must quickly be restored to normal condition
[13]. Hence by using soft-restarting method, one can avoid
such hazards since in soft-restarting, the loads get transferred
to the utility without any transients.
3. Inverter-Coupled Energy Storge
System Contol
In this proposed system, we are using an three -phase three-
level diode clamped inverter to supply ramp power to the load
bus for achieving synchronization with the system. Actually,
the generation of ramp-power is not so easy. It requires certain
control variables for the operation of synchronous reference-
frame phase locked loop (SRF-PLL) and for maintaining the
V/Hz ramp control. SRF-PLL related with ramp control is
shown in figure 3.
As shown in figure 3, the current feedback is only used to
adjust the V/Hz ramp. An open loop V/Hz supply is generated
by the ESS inverter to power up Bus-2 (Load Bus). The
control variables are obtained by abc-to-dq transformation. Vq
and Ѡline are derived from SRF-PLL [14] and are used as
inputs to the Vq-Controller and frequency-controller
respectively. But before these we have to derive the positive
sequence componet of the voltage which is used to fed at the
abc -to-dq transformation. This positive sequence of the
voltage can be derived with the help of sequence analyzer
[15]-[16].
Here we are not using Vd to adjust the magnitude and
frequency of the V/Hz ramp, so it is set to zero. As Vd_inv =
0, hence the inverter output voltage magnitude is:
abc-to-dq transformation also known as Park’s Transformation
[17], which gives line voltages which have been detected as
positive sequence voltages into dq variables as:
Where,
Vabc_line = (rms) magnitude of line-to-neutral voltage at
load bus;
Ѡline = detected line frequency
Ѡinv = detected inverter output frequency
Ɵline and Ɵinv0 = phase angle constant. We select time zero
such that Ɵline = 0 and Ɵinv0 = 0
δ is the voltage angle between Vabc_line and Vinv with phase
angle of 0 degree referred to the ESS bus or load bus. We are
not using d-axis voltage as a control variable for inverter,
hence we will use only equation for further analysis. The phase
angle δ is derived from the transformer coupling impedance
RT
+ jXT. The frequency controller block is used to control the
detected line frequency is as shown in figure 5. In which
output Vq from abc-to-dq transformation is fed to the
controller block, from which we are getting theta (Ɵ). Ɵ is
being used as a control variable for the inverter and is given to
the inverter as an input.
Figure 3. Control schematic of inverter-coupled ESS
International Journal on Applied Physics and Engineering
DOI: 10.37394/232030.2024.3.8
Vikramsingh R. Parihar, Rohan V. Thakur,
Dr. Mohan B. Tasare, Harshada M. Raghuwanshi,
Mohini G. Fuse, Dr. Soni A. Chaturvedi
E-ISSN: 2945-0489
54
Volume 3, 2024
Figure 4. Positive sequence analyzer
Figure 5. Frequency controller
4. Operation During Ramp (V/Hz)
Control
The decaying voltage and frequency at time of fault condition,
given by Vq0 and f0 respectively, have a non-linear
relationship that will highly depend on the inertia of the motor
load connected to the load bus. The operation during ramp
control in which Vq at time t i.e Vq(t) is simply get controlled
by PI controller as shown in figure 6.
Figure 6. Vq controller
Therefore Vq(t) is defined as:
for t = any time in between the operation of ramp control when
inverter supplying ramp power. mvq is slope of the voltage
ramp and it is controlled by PI controller.
Where, t = any time in between the operation of ramp control
and finv = rated inverter output frequency
Equation (5) is used to determine frequency of the inverter
which is then used to determine the angle input (Ɵinv) to the
inverter from:
5. Simulation Parameters and Results
An industrial optimized asynchronous motor is considered as a
load which is driven by load torque given to the shaft and it is
expressed [18] as:
where,
Tinit = initial load torque during startup
TF
= final load torque
= motor speed in rad/sec
TB = base torque in N-m
Table 1: Parameters For Asynchronous Motor
Prated (hp)
400
VLrated
480
f (Hz)
50
N (rpm)
1470
J (kg-m²)
0.089
F(N.m.s.)
0.0065
Rs (Ω)
0.435
Rr (Ω)
0.816
Lls (H)
0.00016
Llr (H)
0.00019
Lm (H)
0.6931
Table II. Transformer Parameters
Rated Power
1.2 MVA
Voltage Rating
2000V/480V, Y-Y
Impedance
4+j3.4%
Table III. Parameters For Ess
Battery Voltage
1.2 MVA
Inverter Switching
500
International Journal on Applied Physics and Engineering
DOI: 10.37394/232030.2024.3.8
Vikramsingh R. Parihar, Rohan V. Thakur,
Dr. Mohan B. Tasare, Harshada M. Raghuwanshi,
Mohini G. Fuse, Dr. Soni A. Chaturvedi
E-ISSN: 2945-0489
55
Volume 3, 2024
Frequency
5.1. During Normal Restarting
At fault condition, CB1, CB2 and CB_main get tripped.
According to the characteristics of their respective fault
clearance timing, each of them clear the fault with respect to
overcurrent and undervoltage of the system condition. So at
normal restarting of the system, it requires much timing for
system restoration and for transferring the load to the utility.
Hence during normal restarting of the system, corresponding
voltage and current results are as shown for the proposed
system which is simulated using MATLAB/SIMULINK.
Figure 7. Rated voltage
Figure 8. Output voltage at load bus during normal restarting
Figure 9. Output current at load bus during normal restarting
5.2. During Soft-Restarting
The output results for soft-restarting method is as shown
below, in which the time required for the system to close and
to transfer the load to the utility get reduced, hence better and
fast service restoration is achieved. Also for the current output,
the transients which were noticed even after the normal
restarting of the system get overcome and time required is also
less as compared to normal restarting method.
Figure 10. Output voltage at load bus during soft-restarting
Figure 11. Output current at load bus during soft -restarting
Figure 12. Output Positive sequence voltage
Figure 13. Output voltage from abc to dq transformation
International Journal on Applied Physics and Engineering
DOI: 10.37394/232030.2024.3.8
Vikramsingh R. Parihar, Rohan V. Thakur,
Dr. Mohan B. Tasare, Harshada M. Raghuwanshi,
Mohini G. Fuse, Dr. Soni A. Chaturvedi
E-ISSN: 2945-0489
56
Volume 3, 2024
Figure 14. Inverter output voltage
Figure 15. Output rotor current
Figure 16. Output stator current
Figure 17. Motor speed
Figure 18. Electromagnetic torque output
6. Conclusion
For transient-free load transfer in industrial power network, a
system is proposed in this paper. The res ults are simulation
based which are obtained for the proposed system parameters.
The current transient during normal restarting and during soft
restarting has been compared, by which we come across the
fine results of soft-restarting in which current trans ients are
get reduced and the time required for the system restoration is
also get reduced. Hence this method is reliable in case of
industrial loads for acquiring service restoration after fault as
quick as possible.
References:
[1] K. Maslo and V. Gromnica, "Power System Dynamic
Model as a Digital Twin," 2024 24th International
Scientific Conference on Electric Power Engineering
(EPE), Kouty nad Desnou, Czech Republic, 2024, pp. 1-6
[2] T. Wagner, Ch. Kittl, J. Jakob, J. Hiry and U. Häger,
"Digital Twins in Power Systems", IEEE power & energy
magazine, vol. 22, no. 1, Jan./Feb. 2024.
[3] "VDE Study Offenbach am Main" in Available: VDE
Study - The Digital Twin in the Network and Electricity
Industry, Germany, May 2023
[4] M. Slámka, "Real Time Dispatch Training Simulator
based on TRIS/DMES", Proc. IFAC CIGRE/CIRED
Workshop on Control of Transmission and Distribution
Smart Grids, 2016.
[5] J. Koudelka, S. Macejko, P. Toman, T. Hába and K.
Máslo, "Simplified Dynamic Model for Continental
Europe Synchronous Area Separation", Proc. 22ndInt.
scientific conference Electric Power Engineering, 2022.
[6] J. Koudelka, B. Bátora, S. Macejko, P. Toman, T. Hába
and K. Máslo, "Multi area dynamic model for Continental
Europe synchronous area splitting", Proc. 23rdInt.
scientific conference Electric Power Engineering, 2023.
[7] K. slo, J. Koudelka, B. Bátora and V. Vyčítal,
"Asymmetrical three-phase power system model: design
and application", Acta Polytechnica Hungarica, vol. 20,
no. 11, 2023.
[8] M. Zavřel, V. Kindl and M. Frivaldský, "Feasibility Study
of Dynamic Wireless Power Transfer Based on AC Power
Distribution Bus and Matric Converter," 2024 ELEKTRO
(ELEKTRO), Zakopane, Poland, 2024, pp. 1-6
[9] Hussein T. Mouftah, Melike Erol-Kantarci and Mubashir
Husain Rehmani, "Wireless Charging for Electric
Vehicles in the Smart Cities: Technology Review and
Impact", Transportation and Power Grid in Smart Cities:
Communication Networks and Services Wiley, pp. 411-
426, 2019.
[10] C. Panchal, S. Stegen and J. Lu, "Review of static and
dynamic wireless electric vehicle charging system", Eng.
Sci. Technol an Int J., vol. 21, no. 5, pp. 922-937, 2018.
International Journal on Applied Physics and Engineering
DOI: 10.37394/232030.2024.3.8
Vikramsingh R. Parihar, Rohan V. Thakur,
Dr. Mohan B. Tasare, Harshada M. Raghuwanshi,
Mohini G. Fuse, Dr. Soni A. Chaturvedi
E-ISSN: 2945-0489
57
Volume 3, 2024
Contribution of Individual Authors to the
Creation of a Scientific Article (Ghostwriting
Policy)
The authors equally contributed in the present
research, at all stages from the formulation of the
problem to the final findings and solution.
Sources of Funding for Research Presented in a
Scientific Article or Scientific Article Itself
No funding was received for conducting this study.
Conflict of Interest
The authors have no conflicts of interest to declare
that are relevant to the content of this article.
Creative Commons Attribution License 4.0
(Attribution 4.0 International, CC BY 4.0)
This article is published under the terms of the
Creative Commons Attribution License 4.0
https://creativecommons.org/licenses/by/4.0/deed.en
_US
International Journal on Applied Physics and Engineering
DOI: 10.37394/232030.2024.3.8
Vikramsingh R. Parihar, Rohan V. Thakur,
Dr. Mohan B. Tasare, Harshada M. Raghuwanshi,
Mohini G. Fuse, Dr. Soni A. Chaturvedi
E-ISSN: 2945-0489
58
Volume 3, 2024